Field glossary · measurement
kW per rack
Rack density assigns an electrical power rate to one cabinet under a named operating condition. State whether the figure is reserved capacity, measured average, coincident peak or a controlled power cap. A 120 kW rack measured at its AC inputs is different from 120 kW of GPU allocations; power conversion, CPUs, switches and standby components also consume part of the cabinet budget.
Power drawn by a single cabinet, the design number for feeder, busway, and cooling sizing
Define what sits inside the rack power boundary
NVIDIA’s published DGX GB power-shelf configuration uses AC input converted to nominal 50 to 51 V DC, while its Mission Control 2.0 GB200 NVL72 example budgets approximately 120 kW for the rack at full load. Identify that platform and operating state on the schedule; neither component telemetry nor another rack generation inherits the same AC demand.
The same NVIDIA guide specifies eight shelves containing six 5.5 kW supplies each, arranged for N+N redundancy. Multiplying those supplies gives 264 kW of installed nameplate capacity, not a 264 kW operating rack load. Redundant hardware capacity and measured consumption belong in separate columns.
Allocate overhead when scheduling work by compute node
NVIDIA Mission Control 2.0’s GB200 NVL72 example divides approximately 120 kW across 18 nodes, assigning about 6.7 kW per node including external rack components. Its reservation model identifies 6.1 kW of managed CPU and GPU power and approximately 0.6 kW of static power per node.
Eighteen allocations of 6.7 kW total 120.6 kW because the per-node figure is rounded. Preserve the unrounded budget or the authoritative rack total when reconciling the model. Adding a rounded component sum to the rack total would count the same allowance twice.
Report the densest cabinet alongside the row average
A row containing nine 10 kW cabinets and one 120 kW cabinet totals 210 kW, averaging 21 kW per occupied rack. That average conceals the single 120 kW position that determines its local connections and thermal delivery.
List the maximum rack demand, occupied-rack count and distribution of rack loads with the average. Empty reserved positions change the denominator if they are included. Mark the 120 kW position explicitly on the rack readiness layout so its local power and cooling allocation survives a later row-average summary.
Match the time basis across A and B power feeds
Add the real power entering the cabinet on independent feeds at the same time. Two 60 kW normal readings total 120 kW; two feeds each rated to carry 120 kW do not establish 240 kW of cabinet consumption.
Keep normal sharing, single-path operation and workload transitions as separate conditions. A peak recorded on A at one time plus a peak on B at another is not necessarily a coincident rack peak. Synchronized metering gives the actual sum.
Distinctions
- Chip TDP
- A component thermal design figure is not a complete rack AC-input measurement.
- Room W/ft²
- Area density adds a floor-area denominator. A rack value alone does not define aisle space or the total room footprint.
Frequently asked questions
Does a liquid-cooled rack have zero room cooling demand?
Count the components outside the liquid heat-removal path and the rack’s conversion losses. The cooling allocation follows the platform’s documented air and liquid boundaries.
Should rack density include empty cabinets?
State the denominator. Average per occupied cabinet, average per installed cabinet and capacity per reserved position describe different quantities.
Sources checked
Also defined as
- Power density of a cabinet, commonly 10 to 30 kW now, far higher for AI and GPU racks