ANVILFIELD Try FieldOS

Field glossary · data center

Bypass / recirculation

Bypass and recirculation identify air that takes an unproductive route through a data hall. Trace bypass from supply to return around the IT load, and trace recirculation from an exhaust back to a server intake. Measure both routes: a rack inlet above supply temperature can coexist with a cool return. DOE's Return Temperature Index reports their net effect, so even 100% RTI can conceal local mixing.

Supply air that returns uncooling, or hot exhaust that loops back to the inlet; both strand cooling

Used across 2 Anvilfield field guides, most in Datacenter.
Updated

Trace the cool return and the hot inlet separately

EPA ENERGY STAR's airflow guidance identifies bypass as cold supply that does not provide productive IT cooling. Its guidance also distinguishes the tile-placement effects: too few supply tiles at a loaded cold aisle promote recirculation, while too many promote bypass. A hot rack beside a cool return can therefore be an airflow-routing problem even when the plant has ample cooling capacity.

Map the actual supply, equipment inlet, equipment exhaust and unit return positions before comparing their readings. A sensor at the cooling-unit discharge and a sensor at the rack top describe different locations. Record the affected rack and its load alongside the temperatures so a change in fan demand is not mistaken for a change in the air barrier.

Why an RTI of 100 percent does not prove separation

DOE's Data Center Air-Management Tool Engineering Reference, version 1.03, calculates Return Temperature Index as cooling-unit temperature drop divided by equipment temperature rise, using airflow-weighted values and multiplying by 100%. DOE interprets RTI below 100% as net bypass and above 100% as net recirculation. A balanced result describes the aggregate, not the absence of each loss.

With the temperatures below, the cooling-unit drop and equipment rise are both 10 C, producing RTI = 100%. The equipment inlet nevertheless stands 5 C above supply. This net index cannot assign separate bypass and recirculation fractions. Use airflow-weighted averages for the tool's aggregate inputs.

Measurement boundaryTemperature
Cooling-unit supply20 C
Equipment inlet25 C
Equipment exhaust35 C
Cooling-unit return30 C

Use equipment intake compliance as the outcome

DOE's July 2024 data center design guide identifies compliance with equipment intake-air temperature specifications as the ultimate cooling performance measure. Retain inlet evidence at the loaded equipment after an airflow correction, even when the room's average index improves. Averages can improve while the most exposed rack remains hot.

Use the same sensor locations and a comparable operating condition for the before-and-after record. Add the boundary temperatures to the stranded-capacity analysis and connect each repaired opening to the rack readiness record. The result should explain the inlet improvement and return-temperature change at the same measurement positions.

Distinctions

Cooling capacity shortage
Insufficient heat-removal capability at the operating conditions. Routing losses can coexist with that shortage but are not established by the same measurement.
Equipment delta-T
The temperature rise across equipment. A cooling-unit supply-to-return difference crosses another boundary and must be labeled separately.

Frequently asked questions

Can bypass and recirculation cancel in an average?

Their net effect can yield an RTI near 100% while local mixing remains. Keep equipment inlet measurements with the aggregate index.

Does adding airflow fix a hot inlet?

It changes the balance and can increase bypass elsewhere. Identify the local supply and exhaust paths before interpreting the response.

Sources checked

Also defined as

  • Cold air that skips the gear, and hot exhaust pulled back into an intake

Where this shows up

Next step: Browse cooling retrofit bids

Back to the full field glossary