Field glossary · component
CBN
CBN means common bonding network: the building-wide conductive network to which equipment bonding arrangements connect. The useful distinction is topology. A mesh bonded at many points, an isolated network joined at one controlled point, and a DC power return are different arrangements even when they share metalwork. Document the intended connections before interpreting a continuity reading or adding a jumper between systems.
Common bonding network, all the building metal bonded together into one network connected to the grounding electrode system
CBN, mesh-BN and IBN describe different boundaries
ITU-T K.27 (03/2015), which ITU lists as in force, defines an isolated bonding network as having a single-point connection to the CBN or another isolated bonding network. Isolated in this terminology therefore does not mean an unearthed island.
K.27 describes a mesh-BN as interconnected equipment metalwork bonded to the CBN at multiple points. A mesh-IBN also contains an internal mesh, but its interface to the surrounding network remains controlled through the single-point connection. Counting links inside a cabinet row alone will not tell you which architecture the drawings intend.
Mark each equipment-network boundary on the grounding and signal reference drawing, then list every tray, shield and conductor crossing it. Recording those crossings makes an unplanned second bond easier to locate than a cabinet-to-cabinet continuity reading alone.
What a single-point connection window means
ITU-T K.27 gives a typical maximum dimension of 2 metres for the single-point connection window of an isolated bonding network. The window is a physical interface region containing the bonding busbar or frame, rather than a requirement to land every connection on one bolt.
A cable tray crossing the boundary away from that region deserves the same drawing review as a new bonding conductor. An incidental conductive crossing changes the topology even when nobody labels it as a bond. Record boundary crossings, not just the conductor identified as the main bond.
Why the DC return needs its own line on the drawing
K.27 distinguishes a DC-I return, connected to the bonding network at one point, from a DC-C return connected at multiple locations. A return conductor carries operating current; its route cannot be inferred solely from the protective-bond layout.
TIA's current TIA-607 catalog identifies revision E, originally announced in May 2024, for customer-premises telecommunications bonding. At turnover, label protective conductors, telecommunications bonds and DC return conductors separately. Trace each return to its intended network connection; a continuity result alone cannot show whether operating current is following the intended route.
Frequently asked questions
Does a low resistance reading prove the CBN is arranged correctly?
It proves a conductive path between the measurement points under the test conditions. Parallel metalwork can supply that path even when the intended connection is missing or an isolated boundary has been bridged. Interpret the reading with the topology drawing.
Sources checked
Also defined as
- Common bonding network, the grounding mesh each rack bonds to with its own conductor