Field glossary · measurement

RCI

RCI, the Rack Cooling Index, converts equipment-inlet temperatures into two conformance scores: RCI_HI for overheating and RCI_LO for under-temperature conditions. Each score subtracts the accumulated departure from the recommended boundary, normalized by the gap to the allowable boundary and the total number of sampled intakes. The calculation preserves the magnitude of temperature departures, but aggregation can conceal one inlet outside the allowable range even when the overall score is high.

Rack Cooling Index; how well inlet temperatures sit inside the ASHRAE envelope, 100 percent is clean

Used across 2 Anvilfield field guides, most in Datacenter.
Updated

Calculate the hot and cold scores separately

DOE's Air-Management Tool Engineering Reference calculates RCI_HI as 100 × [1 - summed positive excess above the recommended maximum / (N × the gap between allowable and recommended maxima)]. Its cold-side formula is RCI_LO = 100 × [1 - summed positive shortfalls below the recommended minimum / (N × the gap between recommended and allowable minima)].

In DOE's RCI method, N includes every sampled intake, including intakes inside the recommended range. Only the departures outside the applicable recommended boundary enter the numerator. Count temperature measurement points consistently; changing from one reading per rack to three readings per rack changes the sampled population.

Use one temperature unit throughout each calculation. A Celsius numerator divided by a Celsius temperature difference gives a dimensionless ratio. Combining Celsius readings with a Fahrenheit denominator corrupts that ratio even though the final display still shows a percentage.

Ten inlet readings produce an 88 percent RCI_HI

ASHRAE's fifth-edition reference card gives an A1 recommended range of 18°C to 27°C and a low-altitude allowable range of 15°C to 32°C. Using those bounds, take ten inlet readings: eight at 26°C, one at 29°C, and one at 31°C. The hot departures sum to (29 - 27) + (31 - 27) = 6°C.

The denominator is 10 × (32 - 27) = 50°C, so RCI_HI = 100 × (1 - 6/50) = 88 percent. No reading is below 18°C, so RCI_LO is 100 percent. Both warm readings remain below 32°C; the reduced hot score describes departure from the recommended boundary before an allowable-temperature exceedance occurs.

Work the cold side with its own 3°C gap

Replace one of the eight 26°C readings with a 16°C reading, leaving ten points in the survey. The under-temperature sum is 18 - 16 = 2°C and the A1 lower-bound gap is 18 - 15 = 3°C. RCI_LO = 100 × [1 - 2/(10 × 3)] = 93.3 percent. RCI_HI stays at 88 percent because the hot readings did not change.

Using the hot-side 5°C gap for this cold-side calculation would incorrectly return 96 percent. DOE's formulas use separate upper and lower gaps. They also flag RCI_LO with an asterisk when a sampled temperature falls below the allowable minimum, just as they flag a hot-side exceedance.

Why a 98.8 percent score still needs a hot-inlet flag

With the same A1 bounds, 99 readings at 26°C and one at 33°C produce RCI_HI = 100 × [1 - 6/(100 × 5)] = 98.8 percent. The high aggregate score coexists with one inlet exceeding the 32°C allowable maximum.

DOE's engineering reference appends an asterisk to RCI_HI when any sampled intake exceeds the maximum allowable temperature. Report this example as 98.8 percent with that flag, plus the 33°C reading and its sensor location. Start the local investigation with the air-path checks in the airflow overview; a high room score does not clear that inlet.

Keep the sensor population comparable between surveys

Lawrence Berkeley National Laboratory's 2020 temperature-measurement report shows why sensor placement affects the apparent inlet distribution: a scheme aimed at capturing maxima represents a different sample from evenly spaced points across rack faces. Preserve the sensor locations, equipment population, load condition, and chosen temperature bounds with each calculation.

After blanking-panel or airflow work, calculate the comparison from the same locations. Adding many cool sensors while retaining one hot sensor improves an aggregate score through a larger denominator, even when the hot inlet has not improved.

Partition surveys when equipment groups need different allowable boundaries, such as A1 and A4 rows. Publish the selected class, limits, and sample count with each result. A score normalized by a 32°C ceiling cannot be compared directly with one normalized by a 45°C ceiling.

Distinctions

RTI
Return Temperature Index characterizes the air-management heat-rise relationship. RCI evaluates the sampled inlet-temperature distribution against selected boundaries.
Percentage of compliant sensors
A sensor count treats departures equally. RCI includes the size of each temperature departure in its numerator.

Frequently asked questions

Does an RCI of 100 percent prove the whole room is compliant?

Both scores at 100 percent establish that the sampled temperatures meet the selected recommended bounds. Unsampled locations and moisture conditions remain separate measurements.

Can I average RCI_HI and RCI_LO?

Report them separately. Combining them obscures whether the departures occur at the hot or cold boundary.