Field glossary · process
MAC
MAC means move, add, or change when it describes work on a facility’s equipment or cabling. Treat each MAC as a controlled transition between two known configurations, with an authorized target, a recovery path, and evidence that the resulting service works. Updating labels records the final state; it does not by itself establish that the change was safe or successful.
Move, add, or change to the plant; each one ends in an as-built record and label update or the administration drifts
Define the service boundary before touching the patch
A MAC request should identify the service being changed as well as the physical port or cable. Record its current path, destination path, dependencies, approved window, expected interruption, and success criteria. Two identically labeled links can support different tenant or production services, so a physical match is only part of the identification.
Attach the service owner and acceptance result to the cross-connect patch record. This links a change to the person who can confirm the intended service, instead of closing it solely because an interface light returns.
- Authorize: name the service owner, work window, target path, and stop condition.
- Preserve: save readable endpoint identifiers and the approved equipment configuration.
- Accept: test the intended service and reconcile patch records, labels, and configuration changes.
Recurring cabling moves and changes need a repeatable acceptance record; PorchRocket Bid Control shows past public awards so a contractor can identify the agencies buying this service.
Keep a rollback configuration that can actually be restored
NIST SP 800-128 calls for older approved baseline configurations to remain available for review or rollback. Applied to a cabling MAC, preserve the previous endpoint map and relevant equipment configuration before changing either one. A photograph without readable identifiers is not a recoverable baseline.
For a move from panel P1 port 12 to panel P2 port 8, document the original switch port, optical type, patch length, and configuration alongside the new path. If recovery is required, that record identifies the actual earlier state. Reversing only the patch while leaving a changed VLAN or port configuration in place does not restore the same service.
Test, accept, and record emergency changes too
NIST SP 800-128 includes implementation, testing or evaluation, review, and disposition within configuration change control. Use acceptance criteria that exercise the changed service: endpoint reachability, expected routing or segregation, and the relevant physical-link result. Record the result before marking the operational work complete.
NIST SP 800-128 also applies change control to emergency and unscheduled changes. Preserve who authorized the urgent work and reconcile the resulting baseline afterward. TIA's current standard page lists revision D for TIA-606 as of November 5, 2026; its June 19, 2026 notice places TIA-606-E in recirculation ballot and public review. Name the contract's published edition in the cabling records.
Distinctions
- MAC address
- A media access control address identifies a network interface at the data-link layer. It is a different use of the acronym from a move, add, or change work order.
Frequently asked questions
Is a successful link light enough to close a MAC?
It establishes a physical or link-layer condition, depending on the equipment. Complete the specified service checks and reconcile both the physical records and any configuration changed during the work.
Sources checked
Also defined as
- Move, add, or change, the routine reconfiguration work good management makes safe
- Move, add, and change work, the routine changes a DCIM workflow tracks