Field glossary · code or standard
NEC 700 / 701 / 702
NEC 700 / 701 / 702 is the classification an estimator needs before selecting backup-power equipment: emergency loads, legally required standby loads, and owner-selected optional loads have different obligations. The familiar pickup limits are 10 seconds for emergency and 60 seconds for legally required standby; optional standby has no article-wide maximum. One generator can serve several categories, so its nameplate cannot classify every connected circuit.
Emergency, legally required standby, and optional standby articles that set the transfer-time class and the wiring rules
Compare the loads before pricing the transfer equipment
Caterpillar's emergency/standby application comparison identifies 10-second emergency pickup, 60-second legally required standby pickup, and no specified optional-standby pickup time. The application's required response can be faster than the article's ceiling. NFPA's current NEC edition is 2026; the permit's adopted edition remains the basis for the actual alteration.
Use a load schedule with a reason for each classification. The emergency-power guide addresses assignment; the comparison below turns that assignment into bid scope.
| Article and load category | Outage-response basis | Estimator consequence |
|---|---|---|
| 700: Emergency | Code-required life-safety function; 10-second maximum | Include emergency transfer, distribution, and protection obligations |
| 701: Legally required standby | Required backup for the designated function; 60-second maximum | Retain the specified standby equipment and coordination scope |
| 702: Optional standby | Owner-selected continuity; response set by the application | Identify manual versus automatic transfer and the load-capacity strategy |
Quote a breaker change with its coordination review
Cummins' 2026 NEC update explains that 700.32(B) triggers a selective-coordination reevaluation when an emergency-system replacement changes the protective device's manufacturer, type, rating, or settings. A matching 400 A label does not establish equivalent operation.
Under 700.32(C), the same update also identifies modifications, additions, or deletions in the emergency system or its normal supply as review triggers. Include the protection study and resulting settings with the replacement scope. Restricting the quote to exchanging hardware leaves that system decision unresolved.
Single-feeder servicing needs bypass and isolation
Cummins identifies 2026 NEC 700.6(C) as applying to a single emergency feeder in the occupancies referenced by 700.10(D)(1). It requires bypass with continuity of power, prevention of inadvertent paralleling, and isolation of transfer equipment from supply-side and load-side sources.
The same provision requires qualified-person supervision when manual bypass equipment carries the duty while the automatic equipment is disabled for servicing. Include that operating arrangement in the ATS commissioning scope.
A bypassed ATS can still be electrically connected. An isolated ATS has the required connections opened for the defined isolation boundary. Trace both states on the one-line; a bypass handle alone does not demonstrate isolation.
Calculate what automatic optional loads can connect together
Cummins describes 2026 NEC 702.4(A)(2) as allowing full automatically connected load capacity or an energy-management system. The calculation uses Article 120 Parts I through IV or another approved method; the EMS alternatives reference 130.30 or a power-control-system setting under 130.70.
Take a 100 kW source, 80 kW of calculated connected demand, and a proposed 30 kW addition. Simultaneous demand becomes 110 kW, 10 kW above source capacity. Deferring that addition for several seconds does not remove the eventual overlap. The design must establish sufficient capacity or an approved sequence that actually limits connected demand; motor starting and kVA still need their own sizing review.
Carry the admitted loads and shed loads into the standby installation drawings. A spare branch-circuit position answers where a load connects, not whether the source can carry it.
Distinctions
- EPSS classification
- An NEC load category and an NFPA 110 system designation belong in separate drawing fields. Article 700 does not supply the Class runtime value, and a Type 10 designation alone does not identify every downstream circuit's NEC category.
Frequently asked questions
Does an optional standby installation need an automatic transfer switch?
Article 702 includes manual and automatic transfer arrangements. The automatic-connection capacity rule applies when the equipment admits loads automatically; identify that behavior before sizing or adding load.
Where can I obtain the official NEC?
NFPA's document page provides the publisher's edition information and access to the code. Record the edition used for the project alongside the section references.