Field glossary · measurement
Residual pressure
Residual pressure describes delivery under a recorded flow: 42 psig during a 10 gpm draw cannot be compared directly with 34 psig during a 30 gpm draw. The U.S. Fire Administration evaluates hydrant supply against a 20 psi residual benchmark, pairing system pressure with measured or projected flow. A pitot reading belongs to the outlet-flow calculation, so substituting it for the residual gauge changes what the test represents.
The flowing pressure left at a fixture while water is running, what proves the far fixture is served
Pair the pressure with the demand that caused it
A building reading of 42 psig during a 10 gpm draw is not directly comparable with 34 psig during a 30 gpm draw. Record the concurrent demand, supply condition and equipment state. A booster changing speed or a storage tank changing level can shift the pressure while the outlet remains open.
Record the draw-off point and gauge elevation on the building pressure survey. A static-to-residual reduction at one tap includes the supply's response to demand; isolating a pipe section's friction requires upstream and downstream readings during the same flow, with elevation accounted for.
A hydrant pitot reading is not the residual reading
The U.S. Fire Administration's Water Supply Systems, Volume II uses a residual hydrant to observe system pressure while other hydrants discharge. A pitot measures the flowing jet at an outlet to determine flow. Interchanging the two readings corrupts the supply test even though both instruments display psi.
USFA gives outlet flow as Q = 29.83 × C × d² × √p, with Q in gpm, outlet diameter d in inches and pitot pressure p in psi. With a measured 2.5-inch outlet, an appropriate discharge coefficient of 0.90 and 16 psi pitot pressure, the calculated flow is about 671 gpm. The residual gauge elsewhere still supplies the system-pressure coordinate for that flow.
USFA evaluates available fire flow at a 20 psi residual-pressure benchmark. A test reported at 20 psi therefore needs the associated measured or projected flow and the method used. A 20 psi pitot indication is not evidence that the water main retains 20 psi.
The equipment minimum must also be a flowing value
Sloan's Royal 111-1.6-CP-U specification lists a 15 to 80 psi flowing operating range and notes that the connected fixture can require a higher minimum. A 60 psig static reading upstream does not demonstrate that the flushometer receives its required pressure during a flush.
Place the measurement near the equipment connection when diagnosing that equipment. Long branches, a clogged strainer or simultaneous fixtures can create a local deficit that an entry-point gauge never captures. Record which fixtures were operating rather than describing the condition only as 'normal demand.'
Pressure at the test point also cannot be carried unchanged to a higher floor. Elevation and the intervening flow losses remain between the measured residual and the final outlet.
Distinctions
- Static pressure
- The building-water pressure before the test demand begins; useful as a baseline, but it does not establish delivery capacity.
- Pitot pressure
- A jet-velocity measurement used with outlet geometry and a coefficient to determine discharge flow.
Frequently asked questions
Can residual pressure be measured with one tap flowing?
Yes, if the flow and measurement point are recorded. That test describes the one-tap condition; it does not establish pressure during the building’s peak simultaneous demand.
Sources checked
Also defined as
- The flowing pressure left at a fixture with the water running, reserved before any friction is spent
- Pressure left at a fixture while it flows, what has to clear the fixture minimum