Scour velocity
Scour velocity is the speed used to mobilize sediment, which makes discharge rate and pipe bore essential to the flushing record. Gardner, Kansas specifies at least 3 ft/s after water-main disinfection; an 8.00 in. bore needs about 470 gpm to reach that speed. Running 340 gpm longer replaces more water but leaves velocity near 2.17 ft/s. The specified cleaning action and the volume exchanged are different acceptance measures.
The flush velocity, about 3.0 ft/s in recent C651 editions, that lifts and carries debris out instead of rinsing
Convert the velocity target into a measurable flow
The City of Gardner, Kansas, requires at least 3 ft/s for waterline flushing after disinfection in Section 5100, revised September 2022. That is an identified utility requirement, not a claim that every flushing method uses the same target. AWWA currently lists C651-23 as its Disinfecting Water Mains standard; the project's adopted method and utility specification establish the work sequence.
For a circular pipe flowing full, Q in gpm is approximately 2.448 × d² × v, where d is actual internal diameter in inches and v is velocity in ft/s. An 8.00-inch bore needs about 470 gpm to reach 3 ft/s. A measured 340 gpm through that bore produces only about 2.17 ft/s.
Pipe series, wall thickness and lining change the bore. A 7.50-inch internal diameter needs about 413 gpm at 3 ft/s. Using the nominal eight-inch label instead of the actual bore changes the calculated target by roughly 57 gpm in this comparison.
Find the slow section in a mixed-size main
The same flow passes through successive full-pipe sections when no branches are drawing. At a fixed discharge, the larger section has the lower velocity. Meeting a target in a narrow outlet hose says little about the velocity in the main feeding it.
Divide a flushing plan into the pipe reaches actually swept by each valve arrangement. A side branch with no through-flow does not acquire the main's velocity just because the nearby hydrant is open. Attach the active reaches and their controlling bores to the disinfection and flushing record.
Plan the outlet before promising the velocity
Gardner requires acceptance of the hydrostatic test before flushing and prohibits disposal of test water into sanitary sewers. Gardner's Section 5100 also requires at least 24 hours' notice before the flushing operation. Those conditions affect the discharge setup and schedule as directly as the target flow does.
At 470 gpm, a ten-minute run releases about 4,700 gallons. Size and secure the discharge arrangement for that flow and its reaction forces, with the specified chlorine neutralization and erosion control in place. Extending the run time at 340 gpm does not turn the pipe's 2.17 ft/s into 3 ft/s.
Record the flow-measurement method, stable rate, active valve arrangement and run duration. Clear-looking water describes appearance; velocity describes hydraulic action; accepted samples establish the specified water-quality result. None of those records replaces the others.
Distinctions
- Displacement flushing
- Replaces water volume; it can occur below the velocity needed to mobilize settled material.
- Sewer self-cleansing velocity
- An operating criterion for solids transport in a partly full gravity sewer, distinct from a full-pipe water-main commissioning flush.
Frequently asked questions
Can a smaller hose compensate for limited supply?
A smaller hose can increase velocity in the hose while restricting total flow. Calculate velocity in the main from the measured discharge; the outlet jet’s speed is not the main’s scour velocity.
Sources checked
Also defined as
- About 2 ft per second, the flow speed that keeps solids in suspension so the line self-cleans