Field glossary · equipment
UPS
A UPS, or uninterruptible power supply, must cover both the load's power demand and the required time on stored energy. Eaton's 9PX3000RT shows why those checks are separate: at 120 V it is rated 3000 VA and 2700 W, while Eaton estimates 4.8 minutes at 2700 W on internal batteries. Compare watts, VA, battery configuration and operating mode before comparing efficiency figures.
Uninterruptible power supply, which conditions power and carries the load through a source disturbance from stored energy
Check watts and VA before battery minutes
Eaton's July 2023 9PX technical specification rates the 9PX3000RT at 3000 VA and 2700 W for 120 or 125 V output. At 110 V output, the ratings fall to 2700 VA and 2430 W. Record the configured output voltage with the two power limits.
A 2800 W load at 0.95 power factor draws about 2947 VA: 2800 / 0.95. It fits the 3000 VA limit at 120 V but exceeds the 2700 W limit by 100 W. Passing the apparent-power check alone would approve an overload.
Eaton's runtime table estimates 4.8 minutes at 2700 W and 13.9 minutes at 1350 W for the 9PX3000RT on internal batteries. Record battery age, ambient temperature and installed battery modules when comparing a discharge test with those estimates. Halving load does not simply double runtime.
Which edition belongs on a UPS performance declaration?
IEC lists IEC 62040-3:2021, edition 3, as the valid UPS performance and test standard as of November 5, 2026. Its scope covers electronic UPS systems with AC input and output voltages up to 1000 V and energy storage up to 1500 V DC. It excludes stand-alone static transfer systems, rotary UPS and DC-output UPS, which have separate standards.
IEC's published description of the 2021 edition says the performance classification shortened from eight characters to seven when the non-linear step-load type test was removed. Identify the edition on an older eight-character declaration before comparing it with a current declaration. The string length reflects the changed classification scheme; compare the declared behavior within the corresponding edition.
IEC 62040-3:2021 introduced tests for multiple normal modes. Keep each mode's declaration with its intended use in the operating plan. When choosing among the UPS circuit arrangements, compare performance declared for the mode that will actually carry the load.
How load weights change the reported UPS efficiency
ENERGY STAR's Version 2.0 UPS criteria calculate average efficiency from measurements at 25, 50, 75 and 100 percent reference load, using category-specific weights. For AC-output UPS above 10,000 W, the published weights are 0.25, 0.50, 0.25 and zero, respectively. Full-load efficiency consequently has zero weight in that category's average, although it remains a separate measured point.
Efficiency readings of 96.0, 97.0 and 97.5 percent at the first three loading points produce a weighted result of 96.875 percent before reporting-rounding rules: 0.25 x 96.0 + 0.50 x 97.0 + 0.25 x 97.5. This explains why a brochure's highest efficiency number and a loading-adjusted figure need not match.
Preserve the tested input-dependency mode with the efficiency data. Comparing a bypass-based mode on one unit with inverter operation on another mixes two power paths. A project comparison should use the mode the facility intends to run and the load range it expects to carry.
Distinctions
- VFD in a UPS rating
- ENERGY STAR uses VFD to mean voltage and frequency dependent. In motor work, VFD means variable-frequency drive. The same acronym describes two different equipment concepts.
- Battery autonomy
- Autonomy describes stored-energy support time at a stated load. Obtain its runtime curve separately from the normal-mode efficiency declaration.
- UPS redundancy
- Redundant modules share the load differently from a single unit. Use each surviving module's actual loading point when comparing efficiency curves, rather than assigning the system's load percentage to every UPS.
Frequently asked questions
Is a 99 percent UPS efficiency claim enough to compare units?
Record its operating mode and loading point, then compare equivalent data. A maximum value by itself does not identify the measured performance across the intended operating range.
Does a UPS performance certificate replace the site transfer test?
The certificate describes the specified equipment tests. The installed source, bypass and load sequence still needs the site commissioning record.
Sources checked
- IEC: IEC 62040-3:2021 edition 3, scope, status and published changes from the previous edition
- EPA ENERGY STAR: Version 2.0 UPS key product criteria, loading weights and average-efficiency equation
- Eaton: 9PX 700 to 3000 VA technical specification TD153013EN, July 2023, output ratings and battery-runtime table
Also defined as
- Uninterruptible power supply, conditions power and bridges a utility loss on stored energy