VRAM / longitudinal joint sealant

VRAM means void-reducing asphalt membrane, a binder treatment measured by width and pounds per linear foot beneath a planned paving seam. INDOT's 2026 standard HMA rows call for an 18-inch width and 0.95 pound per foot; its coarse-graded rows require more material. Select the mixture row before calculating quantity. Joint adhesive on a cold vertical face is a separate treatment with a different takeoff.

A void-reducing membrane placed hot under the joint before paving; it migrates up into the seam to fill voids and cut permeability

Used across 2 Anvilfield field guides, most in Paving.
Updated

Which specification governs the membrane on this job?

INDOT's 2026 Standard Specifications place the HMA membrane requirements in Section 401.15(b). Its April 2025 Design Memo 25-10 explains the preceding policy change from liquid asphalt sealant to VRAM and the incorporation of recurring provisions into the 2026 book. Use the contract edition and applicable provisions to identify the treatment rather than carrying an obsolete pay-item name forward.

For the Section 401 work discussed here, INDOT applies VRAM beneath longitudinal joints in the top course of category 2, 3 and 4 dense-graded surface mixtures, excluding joints with commercial drives, private drives and mailbox approaches. Locate the specified seams on the paving pass layout before setting out the membrane. Section 410 addresses SMA separately; the HMA rates below are not an SMA takeoff.

Read the application row before calculating pounds

INDOT's 2026 Section 401.15(b) lists an 18-inch membrane width and 0.95 pound per linear foot for the standard HMA cases at planned lay rates of 165 or 220 pounds per square yard. Its coarse-graded cases use 1.26 and 1.51 pounds per foot respectively, with a stated 10 percent rate tolerance. The mixture classification therefore changes the required material quantity even at the same width. In this table, coarse-graded means less than 47 percent passing No. 8 for a 9.5 mm mixture, or less than 39 percent for a 12.5 mm mixture.

For 2,000 feet at 0.95 pound per foot, the quantity at the listed rate is 1,900 pounds before job-specific allowances. At 1.51 pounds per foot, the corresponding quantity is 3,020 pounds. A takeoff that uses only seam length without selecting the correct row misses 1,120 pounds between those two cases. Where the joint joins mixtures assigned different rates, INDOT directs use of the lower rate.

Alignment, yield and core location need different measurements

INDOT's 2026 specification requires the membrane application to be centered within two inches of the joint being constructed. It also requires yield verification within the first 1,000 feet of the day's work and every 12,000 feet thereafter, with one verification for projects shorter than 3,000 feet. Save the weighed collection result separately from a photograph showing alignment.

Keep density cores clear of the membrane footprint

INDOT's 2026 specification excludes density cores within 12 inches of the confined or unconfined edge where VRAM was applied. Mark that exclusion on the sampling plan before selecting core positions. Tie each sample station to the paving joint layout so the acceptance record demonstrates that the location met the specification.

Distinctions

Joint adhesive
Adhesive coats the exposed cold face. VRAM occupies a footprint beneath the seam; its width and pounds per foot are separate quantities from a face-coating takeoff.

Frequently asked questions

Is VRAM the same operation as sealing an existing crack?

No. It is installed before the adjacent paving passes create the joint. Crack sealing treats an opening in pavement that already exists.