Changeover

A two-pipe terminal can call for cooling while its changeover sensor still sees water too warm to enable the cooling valve. On Resideo's TB6575/TB8575 controls, the default cooling and heating thresholds are 60°F and 80°F. Water between them invokes the configured system type's intermediate-temperature behavior. Diagnose that behavior from the pipe reading, purge setting and auxiliary-heat configuration together, rather than from the room setpoint alone.

A two-pipe arrangement that switches the whole zone between chilled and heating water seasonally; four-pipe avoids it

Used across 3 Anvilfield field guides, most in HVAC.
Updated

Which temperature selects heating or cooling?

Resideo's legacy TB6575/TB8575 instructions, revision 62-0311-13, use default pipe thresholds of 60°F for cooling and 80°F for heating. Cooling becomes available below its threshold and heating above its threshold. The manual identifies the product as no longer manufactured; these settings remain relevant when servicing that installed thermostat family.

The same Resideo instructions allow a cooling threshold from 50 to 72°F and a heating threshold from 75 to 90°F. Record both configured values and the sensor reading. A control drawing that says only automatic changeover leaves the technician without the actual decision boundaries used by the terminal.

Why a closed valve can hide the new water temperature

Resideo uses five-minute purges to bring current loop water to an isolated branch sensor. Installer setting 25 offers no periodic purge, a two-hour interval by default, or a 24-hour interval. Disabling periodic purging leaves the other purge triggers active. During the initial purge after installer setup, the valve energizes and the fan stays off.

Johnson Controls' fan-coil piping catalog requires a quarter-inch bleed line for its two-pipe changeover packages using a two-way valve and factory thermostat. The catalog makes that bleed optional with field-provided thermostats. The sensing arrangement explains the difference: a continuously wetted aquastat and a controller that periodically purges a closed branch use different ways to obtain a representative water temperature.

Recognize an intermediate-temperature lockout

Resideo distinguishes two-pipe auto changeover from two-pipe operation with auxiliary heat. If water remains between the thresholds after two five-minute purges, both sequences disable the water-valve output, but their available heating differs.

Read the installer system-type selection before interpreting the valve state. Add that selection and the pipe temperature to the fan-coil valve checkout. Two terminals with the same disabled water valve can have different available heat outputs, as the configuration table shows.

Resideo system typeBetween thresholds after the second purge
Two pipes with auto changeoverFan-only mode; manual fan operation remains available
Two pipes with auxiliary heatWater valve disabled; auxiliary heat remains available for heating calls

Distinctions

Economizer changeover
An economizer changes cooling source according to outdoor conditions. It does not establish whether a two-pipe terminal has heating or chilled water available.

Field example

A TB6575/TB8575 sensor reads 70°F after both five-minute purges, with thresholds still set to 60°F and 80°F. In two-pipe auto mode, the result is fan-only operation. In the auxiliary-heat configuration, the same water reading leaves electric heat available on a heating call. The water temperature alone does not distinguish those outcomes.

Frequently asked questions

Does four-pipe equipment eliminate every use of changeover?

It eliminates the shared water circuit's seasonal conversion. A four-pipe thermostat still chooses between available heating and cooling outputs, using its configured deadband and sequence.

Sources checked

Also defined as

  • The wet-bulb-based control point at which the plant enables or drops free cooling, with an offset and deadband
  • Switching the system between heating and cooling when zones call for opposite modes