Field glossary · measurement
kVA (apparent power)
Apparent power measures the RMS voltage-current burden expressed in kilovolt-amperes. Its relationship to real power depends on true power factor, so the same kW can require different kVA. A 600 kW load at PF 0.75 draws 800 kVA; at PF 0.95 it draws about 632 kVA. The conductor and alternator current change even though the delivered real power stays at 600 kW.
The total the alternator and conductors carry, what the alternator is sized for
Use RMS quantities and identify the meter connection
The Fluke 39/41B manual calculates apparent power as the product of RMS voltage and RMS current. For a single-phase 240 V load drawing 50 A, that product is 12,000 VA, or 12 kVA. It is not automatically 12 kW.
The phase arrangement determines how several voltage-current measurements combine. ABB’s 2023 transformer amperage card calculates balanced three-phase kVA as square root of 3 times line-to-line volts times line amps divided by 1,000. State line-to-line or line-to-neutral explicitly; multiplying three line-to-line voltage-current products would count too much.
With 480 V line-to-line and 100 A balanced current, apparent power is 83.14 kVA. The meter’s actual wiring mode must match the circuit before comparing its aggregate with a calculation. Unbalanced and distorted loads require the meter’s appropriate multiphase measurement method.
Check the kVA setting inside the generator controller
Cummins T-037 bases its full-load generator current reference on the generator’s kVA rating at 0.8 power factor. A controller configured from kW alone can therefore use the wrong current base even while the engine power number looks correct.
Cummins’ worked case pairs a 1,250 kVA, 1,000 kW generator at 480 V with a 1,000 kW resistive bank and identifies the test current as 80% of rated generator current. The calculated currents are approximately 1,504 A rated and 1,203 A on the bank. Include both current bases in the generator acceptance record when reconciling the controller with the load bank.
Use total kVA for nonlinear loads
Fluke distinguishes true power factor, which includes harmonics, from displacement power factor at the fundamental frequency. Using only the displacement value to convert kW to kVA can understate the RMS current burden of a nonlinear load.
For a logged 600 kW and 800 kVA, true PF is 0.75 regardless of a separate fundamental-frequency display. Preserve the meter’s total kVA definition and PF type with the reading. A reconstructed square-root sum of kW and fundamental kVAR is not a substitute for the instrument’s total apparent-power measurement under distorted conditions.
Distinctions
- kVA rating
- A rating is a permitted equipment duty under specified conditions. A live kVA reading is the present burden; its averaging interval matters.
- kVAR
- Reactive power describes a different component of AC power. It does not represent the entire RMS current burden of a distorted load.
Frequently asked questions
Do I add generator kW and kVAR to get kVA?
They are not added arithmetically. The familiar right-triangle calculation applies to the appropriate sinusoidal power components; use total metering for nonlinear loads.
Can a low kW load overload a kVA-limited source?
Yes. Low true power factor raises the current required for that kW. Compare the measured apparent power and individual phase currents with the applicable equipment ratings.
Sources checked