Field glossary · property

MERV

Minimum Efficiency Reporting Value (MERV) uses particle-size performance and, for classes 1 through 4, dust-mass arrestance to place general-ventilation filters on a 1 through 16 scale. ASHRAE 52.2-2025 is the current method. For MERV 13, EPA lists minimum average capture of 50, 85, and 90 percent across the three rated particle-size bands. Select fan capacity using the chosen filter's resistance at scheduled airflow, a separate result from its MERV class.

Minimum Efficiency Reporting Value, the filter's particle-capture rating; higher is finer and more restrictive

Used across 4 Anvilfield field guides, most in HVAC.
Updated

Read all three particle bands behind MERV 13

EPA's MERV reference lists minimum average capture efficiencies for MERV 13 of 50 percent at 0.3 to 1 micrometer, 85 percent at 1 to 3 micrometers, and 90 percent at 3 to 10 micrometers. All three bands matter. A report showing 60, 80, and 95 percent respectively misses the MERV 13 middle-band threshold despite exceeding the other two.

EPA presents those efficiencies as particle-band averages. A 50 percent E1 value does not state 50 percent capture at every diameter inside that band. ASHRAE's June 2025 position document cites 52.2-2025; keep the edition on filter-selection and submittal records so a marketing label cannot stand in for the particle-size test data.

EPA reference class0.3 to 1 micrometer1 to 3 micrometers3 to 10 micrometers
MERV 13At least 50% averageAt least 85% averageAt least 90% average
MERV 14At least 75% averageAt least 90% averageAt least 95% average

Compare rated airflow with initial resistance

Camfil's Durafil ES3 drawing 511475, revision C dated April 10, 2026, lists initial resistance of 0.28 in. w.g. for MERV 13, 0.31 for MERV 14, and 0.65 for MERV 16, each with a plus-or-minus 10 percent tolerance. Its nominal 24 x 24 x 12 inch filter is rated for 2,000 cfm. Those are product-specific resistance values at the stated rated flow, not resistance assigned by the MERV scale.

The nominal difference between the MERV 13 and 14 products is 0.03 in. w.g., but their stated tolerances overlap: 0.252 to 0.308 for MERV 13 and 0.279 to 0.341 for MERV 14. The catalog difference therefore does not guarantee that every MERV 14 sample has more resistance than every MERV 13 sample. Carry the selected model's resistance at design airflow into the duct static-pressure calculation.

Two filter stages do not add their MERV numbers

For one specified particle size, a first stage removing 50 percent leaves half the challenge concentration. A second stage removing 50 percent of what reaches it leaves one-quarter of the original concentration, giving 75 percent combined removal. This follows from successive upstream and downstream counts: combined efficiency = 1 - (1 - first-stage efficiency) x (1 - second-stage efficiency).

That calculation applies to the specified particle size and operating conditions. It does not turn two MERV 8 filters into MERV 16, or establish an assembly rating from two catalog numbers. A rating claim needs the particle-size test results for the claimed device or configuration.

Conditioned efficiency does not specify months of service

ASHRAE's 2024 Handbook identifies Appendix J as optional conditioning reported through MERV-A; it simulates an efficiency loss seen in charged filters without completely removing their fiber charge. Camfil's ES3 drawing reports MERV 13/MERV-A 13A and MERV 14/MERV-A 14A. The matching numbers show that conditioning did not lower these products' reported classes; they do not establish how much dust the filters will hold before replacement.

Frequently asked questions

Does MERV measure dust by weight?

For MERV 1 through 4, yes: ASHRAE's 2024 Handbook identifies average dust-mass arrestance as the classifying metric once clean-filter efficiency in the 3 to 10 micrometer band is below 20 percent. Higher MERV classes use particle-size efficiency. Dust-holding capacity remains a separate accumulated-mass result; a high arrestance percentage alone does not establish fine-particle capture.

Sources checked

Also defined as

  • Datacenter: Minimum Efficiency Reporting Value, the particulate filter rating; gas-phase media is rated separately
  • Minimum Efficiency Reporting Value, the filter efficiency rating; higher catches finer particles

Where this shows up

Related guides

Next step: Map rooftop filter accounts

Back to the full field glossary