ANVILFIELD Try FieldOS

Field glossary · measurement

FLA

FLA, full-load amps, is the motor nameplate current used as a benchmark when comparing operating readings and setting equipment that references that nameplate. A 40 A motor drawing 24 A is at 60 percent of its rated current, but that does not establish 60 percent shaft load. Magnetizing current, supply voltage and part-load efficiency affect the interpretation; an overload dial also needs the specific relay's calibration instructions.

Nameplate full-load amps of the motor, the basis for the overload setting under NEC 430.32

Used across 6 Anvilfield field guides, most in Electrical.
Updated

Why 60 percent of FLA is not 60 percent load

The U.S. Department of Energy's Replacing an Oversized and Underloaded Electric Motor explains that current becomes an unreliable load indicator below about 50 percent shaft load. Even at half load, current remains above half of full-load current because the motor still needs magnetizing current.

A 40 A nameplate motor drawing 24 A is operating at 60 percent of its FLA. That comparison alone does not establish 60 percent shaft load or justify replacing it with a motor 40 percent smaller. Keep the current ratio in the service record as a current ratio. Mechanical output requires a load estimate that includes the motor's part-load behavior.

Include voltage in a motor loading comparison

DOE's amperage-ratio method multiplies measured current divided by nameplate current by measured voltage divided by nameplate voltage. At 24 A measured, 40 A nameplate, 470 V measured, and 460 V rated, that expression is 0.613 rather than 0.600. DOE describes the method as an estimate and provides interpolation using actual half-load current for the 50 to 100 percent load range.

Where input kW is available, compare it with rated shaft kW divided by full-load efficiency. Keep the efficiency's load basis with the calculation: using a full-load efficiency at a lightly loaded condition changes the estimate. The motor nameplate guide identifies the plate fields, while this comparison explains why a normal amp reading still needs operating context.

An overload dial can already include the trip allowance

Schneider Electric's Motor Logic guidance specifies a dial setting equal to nameplate current for service factors of 1.15 to 1.25, and 90 percent of nameplate current for a 1.0 service factor. Those instructions apply to its 9065 solid-state overload family. On that family, a 40 A motor with a 1.0 service factor produces a 36 A dial setting.

Do not transfer a trip-current percentage directly onto a dial calibrated in motor amperes. Record the relay family, dial value, service factor, and instruction reference together. A replacement relay with a different calibration can need a different dial value for the same motor. This detail belongs beside the settings used during MCC commissioning.

Distinctions

Measured running amps
A clamp reading follows the present load and supply conditions. The nameplate value remains the reference for that motor and rated voltage; replacing the motor can change that reference even when the horsepower is unchanged.

Frequently asked questions

Can a motor below FLA still be too large for the load?

Yes. A lightly loaded induction motor continues to draw magnetizing current, so reduced amp draw does not by itself quantify spare horsepower. Compare measured input power and the motor load curve before selecting the replacement rating.

Sources checked

Also defined as

  • HVAC: Full-load amps on the nameplate, the current a motor or compressor should not exceed in service
  • Full-load amps, the rated current on one side at rated kVA and that side's voltage

Where this shows up

Next step: Find rooftop motor accounts

Back to the full field glossary