ANVILFIELD Try FieldOS

Datacenter

Data center rack PDU types and power distribution field guide

Select a server rack power distribution unit (PDU) by matching supply voltage, usable amperage, input connector, outlet ratings, and certification to the rack load after a feed failure. The rack power strip and how to pick one: basic, metered, switched, and intelligent PDUs, 0U vertical versus horizontal, single versus three-phase, the A and B feeds, the input and outlets, and the spec that controls the call.

Rack PDUData CenterPower DistributionIntelligent PDU3-Phase Power

Direct answer

Choose a server rack PDU by matching its input and outlet voltages, connector and cord ratings, usable current at every limiting component, monitoring functions and model certification. Verify the complete rack load on each surviving A/B path. A rack PDU distributes branch-circuit power to equipment cords; a floor PDU distributes power upstream and often includes a transformer. Feature names vary by manufacturer.

On this pageWhat a rack PDU is and where it sits in the power chainWhat is the difference between a rack PDU and a floor PDU?Metering, switching and monitoring featuresThe metered PDU and rack capacityThe switched PDU and remote outlet controlThe intelligent or managed PDUWhat is a 0U PDU?Single-phase versus three-phase rack PDUsPhase balancing on a three-phase stripWhich voltage and connector ratings must match?The input: plug, cord, and voltageThe outlets: C13, C19, count, and lockingThe A and B feeds and dual-corded serversThe redundancy budget and the static transfer switchWhich UL listing and NEC edition apply?Continuous-load capacity and listed assembly conditionsHow many amps does a 6 kW rack need after an A/B failure?High-density and AI rack powerHow does rack PDU monitoring and alerting work?Installing and cabling the rack PDUHow do I choose a rack PDU?Rack PDUs at data-center scaleWhat should a rack power upgrade quote include?What to documentCommon mistakesField checklistMethodologyStandards and referencesUnits, terms, and acronyms

Key takeaways

  • A rack PDU is the power strip inside a server cabinet, the last step before the IT load, fed from the floor PDU, RPP, or busway.
  • Rack PDUs come in four intelligence levels: basic (outlets and breaker), metered (current readout), switched (remote outlet control), and intelligent (metering, switching, and sensors over the network).
  • Hold continuous load to 80 percent of the breaker rating, so a 30A strip carries about 24A, per the NEC and UL convention.
  • Use single-phase below roughly 5 kW and three-phase above it; 415V three-phase roughly doubles capacity over 208V at the same amperage.
  • A and B feeds make a rack redundant only when both strips trace to genuinely separate paths and each side is loaded to about half its capacity.

What a rack PDU is and where it sits in the power chain

A rack PDU is the power strip inside a server cabinet. It takes power from the floor PDU, the RPP, or the overhead busway and splits it into the outlets the servers' power supplies plug into. That makes it the last piece of the power chain before the IT load. Everything upstream, the utility, the generators, the UPS, the floor PDU, exists to get clean power to this strip, and this strip is what hands it to the gear.

Keep the two PDUs straight, because the same three letters get used for both. The floor PDU is the transformer-based cabinet out on the floor, covered in the PDU and RPP commissioning guide. The rack PDU is the strip inside the cabinet, and that is what this guide is about. When a drawing says PDU, find out which one before you order anything or quote anything.

The strip looks simple, and it is not where most people expect trouble. The trouble is choosing the wrong intelligence level and stranding capacity, sizing the input too small for the rack that fills in two years, or running A and B strips that are not actually independent. Those calls all get made before the cabinet is loaded, when changing them is cheap.

What is the difference between a rack PDU and a floor PDU?

The floor PDU is the big distribution cabinet on the floor; the rack PDU is the strip inside the rack. The floor PDU, sometimes drawn just as PDU, takes UPS output, usually steps it through a transformer to the rack voltage, and feeds panelboards or subfeeds that run out to the rows. It is floor-standing gear with a transformer, a main, and breakers. The rack and cabinet selection guide and the PDU and RPP commissioning guide cover that end.

The rack PDU does none of the transforming. It is a power strip, 0U vertical or horizontal, that takes one branch circuit from the floor PDU, the RPP, or a busway tap and breaks it into outlets for the servers. No transformer, no bulk distribution, just the last split to the gear.

The naming collision causes real mistakes. A spec that calls for PDU monitoring might mean branch monitoring at the floor PDU or per-outlet metering at the rack strip, and those are different scopes and different budgets. Read which device the requirement attaches to. The floor PDU feeds the rack PDU feeds the server, in that order, and the word PDU alone does not tell you which link you are looking at.

Metering, switching and monitoring features

Select functions from the model data sheet. Basic, metered, monitored, switched and intelligent are product-family labels, not a universal sequence of capabilities. A monitored unit does not necessarily switch outlets, and an intelligent unit does not necessarily meter every outlet.

Specify the measurement level, network interface, switching rights and sensor support needed by operations. Raritan's technical specifications distinguish inlet and outlet features by model; use that same detail in the purchase schedule.

PDU typeWhat it addsWhere it earns its cost
BasicPower distribution without the specified metering or switching functionsWhere upstream measurement meets the operating plan
Inlet-meteredInput measurements defined by the modelRack capacity tracking
Outlet-meteredMeasurements at identified outletsDevice load and energy tracking
SwitchedRemote control of identified outletsApproved sequencing and remote power operations
Networked or intelligentModel-specific combination of metering, control and sensorsMonitoring integration; verify each required feature

The metered PDU and rack capacity

Inlet metering shows the rack PDU's load at the measured input. Use it together with phase and bank limits before adding equipment. A total-power reading alone does not prove every internal circuit has capacity.

Outlet metering supplies device-level readings where the model supports it. Match outlet identities to equipment tags, and verify accuracy and any contractual billing requirements before using energy readings for chargeback.

The switched PDU and remote outlet control

A switched PDU supports remote outlet control for the outlets identified by its specification. Use it for approved power sequencing, disabling unused outlets or recovery work under the owner's operating procedure.

A dual-corded device requires coordination of both supply paths for a power cycle. Confirm device and outlet identity, authorization and recovery impact before changing power state. Remote switching is an operational control, not an automatic cure for an unresponsive server.

The intelligent or managed PDU

A networked rack PDU reports the measurements and alarms supported by its model. Metering, outlet switching and environmental sensor support are separate features to verify.

Map readings to rack and outlet identities and configure permissions, network security, firmware management and alarm routing. Purchase the functions the operating team will use and the integration it can maintain.

What is a 0U PDU?

A 0U PDU mounts outside the equipment mounting positions, commonly along a rear cabinet channel. It preserves those rack-unit positions but still occupies physical space beside equipment and cords.

Check mounting compatibility, connector depth, rear-door travel, airflow and service clearance with the rack populated. Horizontal units occupy their stated rack space. Outlet count and ambient rating are model-specific, not guaranteed by the 0U label.

Single-phase versus three-phase rack PDUs

Choose phase arrangement from the actual rack load, available circuit and usable equipment ratings. There is no universal 5 kW changeover point. A single-phase rack circuit is also part of an upstream system whose overall phase balance matters.

Anvilfield's 30 A circuit comparison gives 8.21 kW at 208 V three-phase and 16.39 kW at 415 V three-phase for the same 24 A usable line current and 0.95 power factor. Check the PDU's outlet voltage separately: a rack PDU does not normally transform it.

Phase balancing on a three-phase strip

Map each outlet to its phase or line pair and internal bank. Check every line and bank against its permitted current in normal operation and after the specified feed loss. Total rack power does not establish balanced loading.

Alternating outlet assignments simplify distribution but do not guarantee equal load because devices draw different currents. Use measured readings and the equipment schedule. Set imbalance alarms from the operating plan and manufacturer limits; no universal 10 percent acceptance threshold applies.

In a wye arrangement, neutral current includes imbalance and harmonic effects. Include the actual load characteristics and neutral rating in the design review.

Which voltage and connector ratings must match?

Write separate input and outlet voltages on the purchase schedule. A 208 V three-phase delta rack PDU commonly serves 208 V line-to-line outlets. A 400/230 V or 415/240 V wye model serves nominal 230 V or 240 V line-to-neutral outlets and needs the specified neutral. It does not transform the voltage. Confirm each power supply input range; a matching connector does not make 120 V-only equipment suitable for 208 V.

Match the complete input designation, current, voltage, poles, wires, grounding arrangement and cord reach to the installed receptacle. Use approved equipment and cord assemblies for the voltage and load.

Interpower publishes the connector ratings below. These are component ratings, not permission to draw that current continuously from every PDU outlet. The approved cord assembly, outlet, internal bank, and equipment inlet can impose a lower limit. Count one connection per required power supply on each assigned feed, then reserve the owner-approved spare outlets.

Connection at the equipmentInternational component ratingNorth American component ratingSelection check
C13 connector to C14 inlet10 A, 250 V AC15 A, 250 V ACCheck cord-set and PDU outlet limits.
C19 connector to C20 inlet16 A, 250 V AC20 A, up to 250 V ACConfirm the assembly rating and retaining hardware.

The input: plug, cord, and voltage

Match the input plug or inlet, cord assembly, voltage, phase arrangement and current rating to the supplying circuit. Record the complete connector designation and grounding arrangement.

Determine usable current from the manufacturer's rating and the supplying branch-circuit design. A 30 A standard breaker application supplies 24 A of continuous load; a PDU already marked with usable current is not derated a second time.

Trace the source whip or busway tap to the approved one-line. Confirm planned rack growth and available capacity before ordering the PDU and connecting equipment.

The outlets: C13, C19, count, and locking

Match the outlet schedule to the installed equipment cords and complete assembly ratings. IEC 60320 C13/C14 and C19/C20 connections have different current limits; connector shape alone does not establish the usable circuit capacity.

Anvilfield's outlet-count case has 40 dual-corded servers, each requiring a connection on both independent feeds. That is 40 outlets per side and 80 occupied outlets in total, before the owner's spare-outlet allowance.

Use the retaining hardware specified for the outlet and cord combination. Retention reduces accidental disconnection but does not replace cord support or a verified A/B arrangement.

The A and B feeds and dual-corded servers

A/B rack distribution assigns equipment supplies to separate paths within the owner's defined failure boundary. Trace each strip to its source and identify shared upstream equipment. Two cords alone do not establish that the rack survives every upstream failure.

Confirm each equipment supply can carry its assigned load after the other feed fails. Use consistent labels and cord routing, then record the actual source trace. The operating mode of the server supplies determines normal sharing.

The redundancy budget and the static transfer switch

Budget for the complete surviving path. Each required input, internal bank, outlet and cord must carry its assigned failover load. A half-capacity normal-load rule applies only to an equal-sharing arrangement with equal usable path capacities.

Single-corded loads need an approved transfer arrangement where the availability plan requires alternate sources. Verify transfer time, source compatibility and load ride-through against the selected device rather than treating a transfer switch as guaranteed uninterrupted service.

Which UL listing and NEC edition apply?

Use the permit's adopted NEC edition and amendments. The capacity comparison uses the 2023 NEC standard continuous-load branch application. Minnesota applies NEC 2026 to permits filed on or after August 17, 2026, and NEC 2023 to earlier filings.

For the 2023 basis, NEC 210.20(A) sizes branch overcurrent protection for noncontinuous load plus 125 percent of continuous load. Its exception requires the assembly, including protective devices, to be listed for operation at 100 percent of its rating. A larger plug or breaker alone does not establish that qualification.

UL 62368-1, fourth edition dated July 31, 2025, includes rack power distribution subassemblies in its US national differences. UL 1363, sixth edition, covers relocatable power taps rated no more than 250 V AC and 20 A; it is not a universal specification for high-current rack PDUs. Request the exact model certification, applicable standard and edition, installation instructions, rated ambient temperature, and outlet-bank protection schedule. A UL Recognized component mark alone does not establish certification of the complete PDU. Acceptance follows the actual product listing and project requirements, not a generic claim that every PDU must carry the newest standard edition.

Continuous-load capacity and listed assembly conditions

For a standard continuous-load branch application, a 30 A breaker supports 24 A of continuous load and a 20 A breaker supports 16 A. Apply the listed-assembly exception only where its conditions are met. Do not reduce a published usable-current rating a second time.

Check the lowest permitted rating along the supply path: branch circuit, input, internal bank, outlet, cord and equipment inlet. Internal protection and outlet grouping are model-specific. A whole-strip current reading does not establish bank capacity.

A breaker's rating is not a precise overload trip threshold. Use its time-current characteristics and the approved design; an improperly loaded bank can lose power independently of the inlet reading.

How many amps does a 6 kW rack need after an A/B failure?

Anvilfield analysis of a 6 kW rack gives 17.5 A per line on the surviving 208 V three-phase feed. Equal normal sharing gives 8.8 A per feed. The comparable 208 V single-phase feed draws 30.4 A and exceeds the case's 24 A continuous limit.

At 415 V three-phase, the surviving line current is 8.8 A. Confirm the equipment's outlet voltage and neutral arrangement before choosing that supply.

The table evaluates the input circuit. Check every internal bank, cord and outlet separately with the selected PDU's circuit map; input-line currents and line-to-line bank currents are different quantities.

Candidate feedCurrent carrying all 6 kWCalculated input capacity at 24 A and PF 0.95Input-only decision
208 V single-phase30.4 A4.74 kWInsufficient for failover.
208 V three-phase17.5 A per line8.21 kWPasses this input check.
415 V three-phase wye8.8 A per line16.39 kWPasses; verify outlet voltage and neutral.

High-density and AI rack power

High-density rack selection starts with the equipment input schedule and failure-mode load. Evaluate available AC or DC interfaces, power-supply arrangement, cooling and physical access together.

Three-phase rack PDUs are one option for compatible AC equipment. Busbar-fed DC architectures are another. Neither a rack-kW threshold nor an AI label specifies the correct input architecture.

Verify the complete path and monitoring requirements against the accepted equipment configuration. Avoid carrying a generic rack-current allowance into a purchase order.

How does rack PDU monitoring and alerting work?

Rack PDU monitoring is the intelligent strip reporting its readings over the network and raising an alert when a reading crosses a threshold you set. The strip measures current, voltage, power, and energy, per strip and often per outlet, and it watches plug-in sensors for temperature and humidity at the cabinet. Those readings feed DCIM or a building management system, where they sit alongside the floor PDU branch monitoring and the cooling data.

The alerts are what make the monitoring worth anything. Set a warning and a critical threshold per strip and per phase against the breaker rating, so operations gets told before a strip reaches its limit, not after it trips. Set a phase-imbalance alert so a drifting rack flags itself. Set temperature and humidity thresholds at the rack so a cooling failure shows up as an alert naming the cabinet, not as dead gear an hour later. Monitoring with no thresholds is a log nobody reads.

The discipline that makes it useful is the same one that makes branch monitoring useful: the data has to map to the steel. The strip in DCIM has to be tied to the right rack, and the outlet readings to the right gear, or operations gets confident, precise, wrong numbers. Map it, set the thresholds to the ratings, and the strip becomes an instrument instead of a feature on the cut sheet.

Installing and cabling the rack PDU

Mount the PDU using its approved hardware and the cabinet manufacturer's compatible positions. Check clearance with the equipment and cords installed. Verify the supply connector, voltage, phases and grounding through the approved installation procedure before energizing.

The cabling is where a rack stays sane or turns into a trap. Route the cords so they do not cross the airflow path or block the rear door, keep the A cords on the A strip and the B cords on the B strip, and color-code the two sides so the split is visible at a glance. Use the cord locks if the strip and cords support them, because a dropped cord is an outage with no error message. The rack and cabinet selection guide covers the cable management hardware and the channel the cords route in.

Then assign and label. Map each outlet to the gear on it, label the outlet, the cord, and the gear to one naming scheme keyed to the rack coordinate, and write the assignment into the record and the DCIM. A strip whose outlets nobody labeled is a strip where every move turns into a trace-it-out on a live rack, which is where someone unplugs the wrong server. Label as you install, not after the rack is full, because a label filled in from memory later is a guess.

How do I choose a rack PDU?

Start with the equipment load inventory and the required failure cases. Select voltage, phase arrangement and usable current, then match connectors, outlet banks and cords.

Choose mounting from the populated cabinet geometry and choose monitoring and switching from the operating plan. A 0U unit still needs clearance, and a networked unit still needs explicit outlet-feature requirements.

Retain the exact model certification and operating limits. Two PDUs with the same outlet count can have different bank circuits, voltage arrangements and permitted currents.

DecisionWhat drives it
Intelligence levelWhat the room must see and control: capacity, reboot, DCIM
Single vs three-phaseCalculated load, available circuit and failure-case capacity
Voltage and input amperageEquipment input range, circuit design and usable model ratings
Input plugThe receptacle on the whip or busway tap
Form factor0U vertical for a server cabinet, horizontal for two-post
Outlet count and mixC13 and C19 to the gear cords and the redundancy
A and B stripsWhether the rack must ride through a feed failure

Rack PDUs at data-center scale

Standardize approved PDU configurations where the rack loads and interfaces permit it. Record any exceptions, the compatible spares and the settings required by each model.

Map units, circuit names, phase assignments and alarm limits consistently in the monitoring platform. Reconcile readings against the installed circuits before using the aggregated data for capacity decisions.

What should a rack power upgrade quote include?

Price the survey, exact PDU models, whips or receptacle changes, cord sets, outlet mapping, monitoring setup, outage coordination, and witnessed acceptance separately. For contractors pursuing public server-room upgrades, PorchRocket's Bid Control tracks Texas city, county, and school electrical bids. Read the bid documents to establish whether rack PDUs belong to the electrical contractor, IT supplier, or owner; a public listing does not establish an approved equipment substitution or outage window. Carry the rack load schedule and proposed A/B boundary into the estimate so the owner can compare the complete installed scope.

What to document

The rack PDU record is what operations runs the rack against and what the next person reads before they add a server. Capture it per strip, keyed to the rack coordinate, so the strip, its ratings, its feed, and its outlet assignments are on file before the gear lands.

Record the strip type and intelligence level, the input plug, voltage, phases, and amperage, the source whip or busway tap it lands on and whether it is the A or B side, the outlet count and mix, the per-phase and per-side loading, the outlet-to-gear assignments, and the monitoring map and thresholds. The point is that a reviewer can confirm the rack's power from the record alone, without tracing cords on a live rack.

Field to recordWhy it matters
Strip type and intelligence levelTies the rack to what it can meter and switch
Input plug, voltage, phases, amperageConfirms the strip matches the feed and the derated limit
Source feed and A or B sideProves the redundancy traces to two paths
Outlet count and C13/C19 mixConfirms every cord has an outlet
Per-phase and per-side loadingDocuments the balance and the failover budget
Outlet-to-gear assignmentThe map every move and reboot depends on
Monitoring map and thresholdsConfirms the DCIM data matches the rack

Common mistakes

  • Specifying a basic strip where the rack needed metering, so capacity is a guess and the breaker trips or sits stranded.
  • Exceeding the applicable continuous-current limit or derating an already published usable rating twice.
  • Loading both A and B strips near full, so one side failing drops the rack onto a survivor that trips.
  • Leaving the three phases out of balance, so one phase trips while the other two coast.
  • Running A and B strips that trace back to the same floor PDU or upstream breaker.
  • Using incompatible cord-retaining hardware or leaving cords unsupported.
  • Under-sizing the input for the rack the cabinet will hold in two years, forcing a strip and whip swap later.
  • Selecting a mounting position that obstructs airflow, equipment access or the required cord clearance.
  • Energizing intelligent strips without mapping the monitoring to the rack or setting alarm thresholds.
  • Labeling the outlets from memory after the rack is loaded, so the assignments and the gear disagree.

Field checklist

0 of 14 complete

Want this checklist to run itself on every job — with photo proof and a signed record crews can hand the customer? That's FieldOS.

Methodology

Anvilfield research calculates the 6 kW case at the rack AC inputs, including power-supply losses, with 0.95 power factor and continuous operation. Inputs are 208 V single-phase, 208 V balanced three-phase and 415 V balanced three-phase. Each candidate has a 30 A standard branch application with 24 A usable continuous current.

Single-phase current is P / (V x PF); balanced three-phase line current is P / (sqrt(3) x V x PF). Results are 30.3644 A, 17.5309 A and 8.7866 A. Corresponding capacities at 24 A are 4.7424, 8.2141 and 16.3887 kW, rounded to 4.74, 8.21 and 16.39 kW. Equal normal sharing divides full-load current between the two feeds.

The outlet-count case has 40 servers with one supply on each independent feed: 40 outlets per side and 80 in total, before spares. Manufacturer component ratings and UL scope values remain separately attributed; the case arithmetic does not select internal bank or cord limits.

Standards and references

Use the adopted NEC for the circuit and the exact product certification for the rack PDU. UL 62368-1 and UL 1363 have different scopes; the listing must cover the actual device and its intended application.

Match IEC 60320 outlet and inlet components, IEC 60309 or NEMA supply connectors, and complete cord-set ratings. The connector shape does not establish the usable current of the complete path.

The linked manufacturer guidance supports the standard and 100 percent rated continuous-load applications. Use the model's ambient limits, bank schedule and instructions during selection and acceptance.

Units, terms, and acronyms

The rack PDU carries its own vocabulary, and the same strip gets described several ways across a cut sheet, a one-line, and a DCIM screen. Power per rack is stated in kilowatts, current in amps, and energy in kilowatt-hours. Rack height is in rack units, where a 0U strip takes none. Input and outlet types are named by their connector standard. The terms below travel across the selection, the install, and the record.

Rack PDU
The power strip inside a cabinet that distributes a branch circuit to the gear's power supplies
0U / vertical
A PDU mounted outside the equipment rack-unit positions, with physical clearance still required
Metered / outlet-metered
A strip that reads total current at the inlet, or current per outlet
Switched
A strip whose outlets can be turned on and off remotely over the network
Intelligent / managed
A networked PDU with a model-specific combination of measurements, switching and sensor interfaces
A and B feed
Two strips on two independent paths for redundant power to one rack
C13 / C19
IEC 60320 outlets for standard and higher-current server cords
IEC 60309
Industrial pin-and-sleeve connectors identified by their voltage, current and contact configuration
Phase balance
Spreading load across the three phases so no single phase overloads

Related tools

Calculators and readiness checks for this work

Next step: See public electrical bids

FAQ

What is a rack PDU?

A rack PDU is the power strip inside a server cabinet that takes one branch circuit from the floor PDU, RPP, or busway and splits it into outlets for the servers' power supplies. It is the last step in the power chain before the IT load, and it comes in basic, metered, switched, and intelligent versions.

What is the difference between a metered and a switched PDU?

A metered PDU measures the quantities and circuits identified by its model. A switched PDU adds remote control of specified outlets. Confirm inlet, branch and outlet metering separately from switching; the product label does not guarantee every feature.

What is the difference between a rack PDU and a floor PDU?

A rack PDU supplies equipment cords inside the cabinet. A floor PDU distributes power to floor circuits or subfeeds and includes a transformer where its design calls for one. Check the actual voltage and configuration on the submittal.

What is a 0U PDU?

A 0U PDU mounts outside the equipment mounting positions, usually along a rear channel. Verify the mounting hardware, cord depth, airflow, ambient rating and rear-door clearance; outlet count is model-specific.

How many outlets does a rack PDU need?

Count every required supply connection on each feed, then add the owner's spare allowance. Anvilfield's 40-server dual-corded case needs 40 outlets on each side, or 80 occupied outlets in total.

Single-phase or three-phase rack PDU: which do I need?

Choose from the load calculation and available circuit, not a universal rack-kW cutoff. For the Anvilfield 6 kW case at 0.95 power factor, a 208 V single-phase feed draws 30.4 A and a 208 V three-phase feed draws 17.5 A per line.

How much can I load a rack PDU?

Use the lowest permitted current across the complete path. A standard 30 A branch application allows 24 A of continuous load; a qualified 100 percent rated assembly follows its listing conditions. Do not derate an already published usable rating again, and check the full failover load.

What do I do if a server hangs and I cannot reach it?

Follow the owner's recovery procedure. If remote power cycling is authorized and the PDU supports it, verify the device and all of its supply outlets before switching. Dual-corded equipment needs coordinated treatment of both feeds.

Do A and B rack PDUs make a rack redundant?

Only within the verified failure boundary and with adequate surviving capacity. Trace both paths, identify shared upstream equipment and check every input, bank, outlet and cord against the complete failover load. Equal half-load budgeting applies only when sharing and capacities are equal.

Why do rack PDU outlets need to lock?

Compatible retaining hardware reduces accidental cord disconnection. Verify it against the outlet and cord, support the cable, and keep the required A/B connections separate.

People also ask

Codes cited in this guide

This guide is written and reviewed against the published standards below. Always confirm the current adopted edition with the authority having jurisdiction.

Sources checked