ANVILFIELD Try FieldOS

Electrical

Isolated ground receptacles for sensitive equipment

An orange receptacle with a quieter ground path: what an isolated ground really does, why it gets mis-installed more than almost any other device, and where it actually helps.

Isolated GroundIG ReceptacleNEC 250.146Power QualityElectrical

Direct answer

An isolated ground receptacle is an orange device, marked with a triangle, whose ground terminal is insulated from its mounting strap and run back to the source on a separate insulated grounding conductor to reduce electrical noise. It is still a safety ground, not an ungrounded system, and the adopted NEC edition controls how it is wired.

On this pageAn isolated ground, and why the trade keeps getting it wrongWhat makes a receptacle an isolated ground?Why use an isolated ground?An isolated ground is still a safety groundDoes an isolated ground still need a regular ground?The path back to the source: NEC 250.146(D)The orange receptacle and the triangleThe dangerous mistake: an isolated ground as the only groundDo isolated grounds actually reduce noise?Ground loops and common-mode noiseFix the real problem firstClean-power options that do more than an isolated groundThe data center answer: a signal reference gridThe isolated ground bus in the panelHow do you verify an isolated ground?When an isolated ground is specifiedCost, and when it is worth itField checklistWhat to documentCommon mistakesStandards and referencesUnits, terms, and abbreviations

Key takeaways

  • An isolated ground receptacle is an orange, triangle-marked device whose ground terminal is insulated from the mounting strap and run separately back to the source.
  • An isolated ground is still a full safety ground that carries fault current and trips the breaker; it is not an ungrounded or floating system.
  • An isolated ground circuit needs two grounds: the normal EGC that grounds the metal box, plus the separate insulated isolated ground conductor.
  • NEC 250.146(D) permits the insulated isolated ground conductor to pass through panelboards and boxes without bonding, terminating at the source ground.
  • Isolated grounds help only older analog, audio, lab, and medical gear that references its ground; modern switch-mode electronics gain nothing measurable.

An isolated ground, and why the trade keeps getting it wrong

An isolated ground receptacle is a standard-looking outlet, almost always orange and marked with a triangle, whose ground terminal is deliberately insulated from the metal mounting strap and the box. An ordinary receptacle grounds through the conduit and the device yoke. This one does not. Its ground runs back to the source on its own insulated equipment grounding conductor, away from the conduit, the boxes, and every other piece of metal tied into the building grounding. The point is to give sensitive electronics a quieter ground path.

Here is the part that gets it in trouble. An isolated ground is still a safety ground. It is not an ungrounded system and not a floating ground. The device is grounded, just by a separate insulated path instead of the metal raceway.

The trade misunderstands and mis-installs this device constantly. You find them used as the only ground, with the box left ungrounded. You find the insulated conductor scraped bare and touching the conduit, which kills the whole idea. You find them on circuits where they do nothing, installed out of habit because someone read the words sensitive equipment on a cut sheet. For how grounding and bonding actually differ, and where this device sits between them, the grounding-vs-bonding guide is the companion to this one, and the GFCI and AFCI guide covers the protection devices that often share the same circuits.

What makes a receptacle an isolated ground?

An isolated ground receptacle has one feature that defines it: the U-shaped ground terminal is electrically insulated from the receptacle's mounting strap. On an ordinary receptacle that ground terminal is riveted to the yoke, so the moment you screw the device to a metal box, its ground bonds to the box, the conduit, and the building grounding system. On an isolated ground device, the manufacturer breaks that connection inside the receptacle.

So the ground terminal now goes only one place: to the separate insulated equipment grounding conductor landed on it. That conductor runs with the circuit conductors, all the way back to the source ground, without touching the conduit or the boxes along the way.

You confirm the type three ways. The body is orange, or it carries an orange triangle on the face if the plastic is another color. The packaging and the device stamp call out isolated ground or IG. And a continuity check shows the ground terminal is open to the mounting strap, which an ordinary receptacle never is. That last check is the one that catches a plain orange device someone grabbed thinking color alone made it isolated. Color is the label. The insulated terminal is the mechanism, and they are not the same thing.

Why use an isolated ground?

The reason for an isolated ground is electrical noise on the grounding system, nothing else. Every piece of metal bonded into the building ground, the conduit, the boxes, the struts, the panels, carries small currents and picks up interference. For most loads that does not matter. For certain sensitive electronics it does, because the equipment uses its safety ground as a voltage reference for its internal signals, and noise on that ground shows up as noise in the signal.

The classic victims are analog and older single-ended equipment. Audio gear that hums. Lab instruments and medical monitors that drift or show artifacts in the trace. Older data and process equipment that references its signal to chassis ground. In those cases a noisy ground couples straight into the measurement, and a quieter, separate ground path can measurably help.

The mechanism the isolated ground addresses is common-mode noise and ground loops, where two grounded points sit at slightly different potential and current flows on the ground between them. Carrying the equipment ground straight back to the source on its own conductor keeps it out of that loop. That is the whole theory. Whether it works on a given load is a separate question, and the honest answer is often no. The section on whether isolated grounds reduce noise gets into why.

An isolated ground is still a safety ground

This is the point that keeps the isolated ground from being dangerous, and it is the one people forget. An isolated ground is a full safety ground. It carries fault current back to the source and trips the breaker exactly like an ordinary equipment grounding conductor. The only difference is the path it takes to get there.

Do not confuse an isolated ground with an isolated, ungrounded, or floating system. Those are different animals. An ungrounded system has no intentional connection to ground at all and is governed by its own set of rules. An isolated ground receptacle is grounded, fully and intentionally, through its dedicated insulated conductor. If a hot conductor faults to the metal frame of the equipment plugged into it, the fault current has a low-impedance path home and the overcurrent device clears it.

The danger comes only when someone reads isolated as does not need grounding. That misreading is how you end up with ungrounded metal equipment on a bench, waiting for a fault that never trips. The insulated conductor has to be continuous, sized as an equipment grounding conductor, and landed on the source ground. Isolate the path, never the safety function. If you remember one sentence from this guide, that is the one.

Does an isolated ground still need a regular ground?

Yes, and this is the part that trips up even experienced installers. An isolated ground circuit has two grounds at the box, and both have to be there. The first is the normal equipment grounding conductor, the conduit or a separate green wire, which grounds the metal box, the cover, and any other metal at the outlet. The second is the insulated isolated ground conductor, which serves only the receptacle's ground terminal and runs back to the source.

Skip the box ground and you have a real hazard. The metal box and faceplate are no longer grounded, because the isolated ground inside the receptacle is insulated from the strap and does nothing for the box. A fault to the box has no path home. The receptacle is protected. The box is not.

So the box gets grounded the ordinary way, by the metal raceway or its own EGC, and the isolated ground conductor runs alongside as a separate, additional conductor. Two grounds, two jobs. One keeps the enclosure safe, the other gives the receptacle its quiet path. Run only one and you have either an ungrounded box or an isolated ground that is not isolated. There is no version of this circuit that works with a single ground conductor.

The path back to the source: NEC 250.146(D)

The rule that permits the isolated ground is commonly found at NEC 250.146(D), the subsection on isolated ground receptacles within the general grounding-of-receptacles section. It allows the receptacle's grounding terminal to be connected to an insulated equipment grounding conductor run with the circuit conductors, separate from the conductor that grounds the box and raceway.

The useful part is what it lets that conductor do. The insulated isolated ground conductor is permitted to pass through one or more panelboards without connecting to the panelboard grounding bar, and through boxes and wireways without bonding to them, so it can run straight back to terminate at the equipment grounding terminal of the applicable derived system or service that supplies the circuit. The pass-through permission ties to the panelboard rule, commonly the exception at 408.40. The conductor has to stay insulated the entire way and has to terminate within the same building or structure.

That is the design intent: one continuous, insulated, quiet ground from the receptacle back to the source ground, bypassing every intermediate bond. The landing point matters. The conductor goes to the ground of the system that actually feeds the circuit, not to a convenient bar partway there. Section numbers move between code cycles, so confirm 250.146(D), 408.40, and the related sections against the edition the jurisdiction has adopted before you cite them on a submittal.

The orange receptacle and the triangle

An isolated ground receptacle has to be identified, and the identification is the orange triangle. The marking requirement is commonly found at NEC 406.3(D) in recent editions, calling for the receptacle to be marked with an orange triangle on its face. In practice the whole device body is usually orange, which is why the orange receptacle is shorthand for an isolated ground in the field.

The marking exists so the next person knows what they are looking at without pulling the device. An isolated ground circuit looks ordinary from the cover plate, and the wiring behind it is different in a way that matters to anyone troubleshooting or extending it. The triangle is the flag.

Two cautions. First, an orange receptacle is not automatically an isolated ground. Some orange devices are just orange, or are a hospital-grade type in a color that happens to match, so verify the insulated ground terminal and do not trust the color. Second, the section number and the exact marking language have shifted across code cycles, so confirm the marking requirement against the adopted edition. The triangle is the constant. Confirm the device is genuinely isolated, then make sure it carries the mark so the record matches the metal.

The dangerous mistake: an isolated ground as the only ground

The worst isolated ground error is using it as the only ground and leaving the box ungrounded. It happens because the wiring looks complete. The receptacle has a ground, the circuit works, a plug-in tester shows a ground present at the outlet. What the quick check misses is that the metal box, the conduit, and the faceplate have no ground path of their own.

Picture the failure. A hot conductor chafes against the metal box. On a properly grounded box the fault current dumps to the EGC and the breaker trips in a cycle or two. On a box grounded only through an isolated ground receptacle, the box is insulated from that ground inside the device, so the fault sits there. The box is energized, the breaker is happy, and the next person to touch the cover plate is the fault path.

This is why the two-grounds rule is not optional. Ground the box the normal way, every time, then add the isolated ground conductor as the separate path for the receptacle. If you ever find an isolated ground receptacle feeding a metal box with no other EGC, treat it as an open box ground and fix it before anything plugs in. That is a shock hazard, not a noise problem, and it does not wait for a convenient time to bite.

Do isolated grounds actually reduce noise?

Often they do not, and that is the honest answer the cut sheets leave out. An isolated ground helps only when the noise problem is genuinely on the equipment ground and the equipment actually references that ground for its signals. A lot of modern electronics do neither.

Most current equipment runs on a switch-mode power supply that is isolated from earth and does not use the safety ground as a signal reference. For that gear the ground is purely a safety connection, and a quieter ground path changes nothing you can measure. Installing an isolated ground on a rack of modern servers or a typical office computer is usually money spent on a conductor that does no work.

Where it can still help is the older analog and single-ended equipment named earlier, and even then only if the ground really is the noise entry point. The mistake is cargo-culting it: specifying isolated grounds across a whole floor because one instrument once had a hum, or because the word sensitive appeared in a spec. Before you wire a building full of orange receptacles, prove the noise is on the ground and prove the equipment cares. Most of the time the noise is somewhere else entirely, which the next section covers.

Ground loops and common-mode noise

A ground loop is current flowing on a grounding conductor because two points that are both grounded sit at slightly different voltage. Tie two pieces of equipment together with a signal cable, ground each one separately, and if those two grounds are not at exactly the same potential, a small current circulates through the signal cable's shield and the grounds. In analog and audio systems that circulating current shows up as hum, or as a baseline offset in a measurement.

The isolated ground attacks one version of this by giving the equipment a single, dedicated ground path back to the source instead of many parallel paths through the building steel. Fewer paths, fewer loops. In theory the equipment ground stays cleaner because it is not sharing a noisy network of bonded metal.

The catch, and the Emerald Book is blunt about this, is that ground loops are not always bad. For high-frequency digital signaling you want many short ground connections and the loops that come with them, because they equalize potential at high frequency. So the same isolated ground that quiets a low-frequency analog loop can be the wrong move for high-speed digital gear. The frequency of the noise decides whether isolating the ground helps or hurts, and assuming it always helps is how good intentions make a system worse.

Fix the real problem first

Most we-need-isolated-grounds calls are really something else, and an isolated ground receptacle will not touch the actual cause. Before you spend the conductor, find the noise source.

The usual culprits are not the equipment ground at all. A shared neutral that is overloaded or carrying harmonic current puts voltage on the neutral and the connected equipment. Harmonics from electronic loads, drives, and power supplies distort the system and heat neutrals. A data or signal grounding problem, where the noise rides the signal cable shields rather than the power ground, is common, and an isolated power ground does nothing for it. Poor terminations, a high-impedance ground, or a plain wiring error can all read as noise to the person whose equipment is acting up.

An isolated ground only addresses noise that is on the equipment grounding conductor and coupling into equipment through that ground. If the problem is a shared neutral, you separate the neutrals or rebalance the load. If it is harmonics, you look at the neutral sizing, the transformer, and filtering. If it is signal grounding, you fix the signal grounding. Wiring an orange receptacle and walking away just hides the fact that nobody found the root cause, and the complaint comes back a month later with the same symptom and a new work order.

Clean-power options that do more than an isolated ground

When a load genuinely needs clean power, the heavier solutions do more than an isolated ground receptacle, and an engineer will usually reach for them on a serious problem. The isolated ground is the lightest tool in the box.

A dedicated circuit, just that load on its own breaker and neutral, removes the noise other loads dump onto a shared branch and solves a lot of what people blame on the ground. An isolation transformer goes further. It creates a separately derived system with its own grounding point close to the load, which breaks the noise path from the rest of the building and gives a short, clean ground reference. For a cluster of sensitive equipment that is the real fix, not a single receptacle. A line conditioner or a UPS with filtering deals with sags, surges, and distortion that grounding alone cannot.

These overlap with grounding-and-bonding fundamentals, because a separately derived system has its own bonding and grounding rules at the transformer, which the grounding-vs-bonding guide walks through. The point is to match the tool to the problem. An isolated ground addresses noise on the ground path. A dedicated circuit, an isolation transformer, and conditioning address the larger power-quality picture, and for most real complaints they earn their cost where a lone isolated ground would not.

The data center answer: a signal reference grid

A modern data center does not solve noise with isolated ground receptacles scattered across the floor. It uses a signal reference grid, sometimes called a signal reference structure or zero reference grid, described in IEEE 1100, the Emerald Book. The grid is a dense mesh of bonding conductors, often the bolted-together access floor or a copper grid under it, tying all the equipment to a common reference.

The reason is frequency. At high frequency a single long ground conductor has too much impedance to keep equipment at the same potential, so a lone isolated ground actually performs worse than a grid. The mesh gives many short, low-impedance paths, so every cabinet sits at effectively the same reference across a wide frequency range. That is the opposite philosophy from a single isolated path, and for high-speed digital equipment it is the correct one.

This is worth knowing even on smaller jobs, because it is where the isolated ground myth breaks down hardest. For one quiet analog instrument, a dedicated isolated ground can help. For a room full of high-speed digital gear, the answer is bonding everything together into a low-impedance grid, not isolating each piece. Same goal, opposite method, and the equipment frequency decides which one is right.

The isolated ground bus in the panel

When isolated grounds are done at scale, the panel gets a second ground bar. Alongside the normal equipment grounding bar that is bonded to the enclosure, the installer adds an insulated isolated ground terminal bar, mounted so it does not bond to the cabinet. Every isolated ground conductor from the branch circuits lands on that insulated bar.

From there the isolated ground bar is carried back to the source ground on its own conductor, either to the service or to the separately derived system that feeds the panel, passing through any intermediate panelboards without bonding, the same permission that lets the branch conductor pass through. The whole isolated ground system stays separate from the normal grounding all the way back to one common point at the source, where everything finally ties together. That single common point is what keeps the isolated ground from becoming an unsafe, disconnected subsystem.

The detail people miss is at that insulated bar. If the bar touches the cabinet anywhere, through a mounting screw or a bent conductor pinched against the can, the isolation is gone and you have built an expensive ordinary ground. Verify the bar is genuinely floated from the enclosure and that the run back to the source is continuous and correctly sized. One stray contact undoes every isolated ground on the panel.

How do you verify an isolated ground?

Verifying an isolated ground means proving two separate things: the isolated path is continuous and isolated, and the box has its own ground. Check both, because each can fail without the other showing.

Start de-energized for the isolation check. With the receptacle out, confirm the ground terminal is open to the mounting strap with a continuity tester or ohmmeter. A reading near zero means the device is not actually isolated or is wired wrong. Trace the insulated isolated ground conductor and confirm it is unbroken back to the source ground, not landed on an intermediate panel bar, and not nicked where it crosses conduit. Then confirm the box itself is grounded by the normal EGC, separately from the isolated ground.

Energized, a plug-in tester will show a ground present but cannot tell an isolated ground from an ordinary one, and cannot confirm the box is grounded, so do not rely on it alone. For a real check, measure the ground impedance back to the source and look for a low, clean value, and on a noise complaint measure the actual voltage between equipment ground and the source reference under load. If the isolated ground reads a higher impedance than the normal path, something in that long single conductor is loose, undersized, or open.

When an isolated ground is specified

An isolated ground is usually an engineer's call, not a field add-on. It shows up on the drawings or in the spec for a specific piece of equipment with a documented sensitivity, and when it is called out, install it exactly as drawn: insulated terminal, separate insulated conductor, box grounded the normal way, run back to the designated source.

What you should not do is add isolated grounds on your own judgment because a load looks delicate or because orange receptacles were left over from another job. The isolated ground is a design decision that depends on the equipment, the noise environment, and the grounding scheme of the building. Adding one where it was not engineered can do nothing at best and create an ungrounded box at worst.

It runs the other way too. If a spec calls for isolated grounds across an entire floor of modern digital equipment, that is worth a question to the engineer, because it is often a default copied from an old template rather than a response to a real problem. Install what is engineered, flag what looks like cargo cult, and keep the judgment calls with the person who owns the design and the liability that comes with it.

Cost, and when it is worth it

An isolated ground costs more than an ordinary receptacle, and the cost is mostly the extra conductor and the labor to run it. Every isolated ground circuit carries a separate insulated grounding conductor the full length back to the source, on top of the normal EGC, plus the premium device, plus the isolated ground bar in the panel at scale. On a long run that second conductor is real money and real pull time.

It is worth it only for a real, identified noise problem on a load that actually references its ground. For that case the cost is trivial against an instrument that will not read straight or a process that keeps faulting. For everything else, which is most outlets, it is money spent on a conductor that does no work and a slightly higher chance of a wiring mistake at the box.

The decision is the same one that runs through this whole guide. Prove the noise is on the ground, prove the equipment cares, and confirm an isolated ground is the right tool against a dedicated circuit or an isolation transformer. If you cannot show those three, the cheaper and safer move is an ordinary, well-grounded circuit and the time spent finding the actual noise source.

Field checklist

0 of 9 complete

Want this checklist to run itself on every job — with photo proof and a signed record crews can hand the customer? That's FieldOS.

What to document

An isolated ground that nobody can explain later becomes a mystery the next electrician has to reverse-engineer. The record answers two questions down the road: why the circuit was built this way, and whether it is still safe and still doing its job.

Field to recordWhy it matters
Equipment served and its documented sensitivityShows why an isolated ground was used at all
Who specified itTies the isolated ground to a design decision, not a guess
Isolated ground conductor size and insulationConfirms it is a code-sized, insulated grounding conductor
Termination point at the sourceProves it runs back to the service or derived system ground
Box ground methodShows the enclosure is grounded separately from the isolated ground
Isolation continuity check resultRecords that the ground terminal is open to the strap
Ground impedance or noise readingBaseline to compare against if the noise returns

Common mistakes

  • Using the isolated ground as the only ground, leaving the metal box and faceplate ungrounded and unsafe.
  • Letting the isolated ground conductor touch the conduit or a panel ground bar, which defeats the isolation.
  • Installing isolated grounds where they do nothing, on modern switch-mode equipment that does not reference its ground.
  • Trusting an orange body for the marking, when only a genuine insulated ground terminal makes the device isolated.
  • Relying on an isolated ground instead of finding the real noise source: a shared neutral, harmonics, or signal grounding.
  • Failing to carry the isolated ground conductor all the way back to the source ground.
  • Landing the isolated ground on an intermediate panel's normal ground bar instead of running it through to the source.

Standards and references

The framework lives in the NEC, NFPA 70. The isolated ground receptacle permission is commonly at 250.146(D), which allows the insulated isolated ground conductor and lets it pass through panelboards and boxes without bonding to terminate at the applicable derived system or service ground. The panelboard pass-through ties to the exception commonly at 408.40. The deeper case, isolating the equipment enclosure itself from a metal raceway with a listed nonmetallic fitting plus an internal insulated equipment grounding conductor, is commonly at 250.96(B). The receptacle marking, the orange triangle, is commonly at 406.3(D) in recent editions. Health care facilities carry their own rules on isolated grounds, commonly in Article 517.

For the power-quality engineering behind it, IEEE 1100, the Emerald Book, is the reference for powering and grounding electronic equipment, including isolated grounds, signal reference grids, and when each applies. It is also clear that isolated grounding subsystems left unconnected are unsafe, and that every grounding subsystem has to tie back to a common point.

Section numbers shift between code cycles and jurisdictions amend the NEC, so confirm 250.146(D), 250.96(B), 408.40, 406.3(D), and any Article 517 rules against the adopted edition and the AHJ before you cite them on a submittal. Across all of it, three things hold. An isolated ground is still a safety ground and the box still needs its own equipment grounding conductor. The isolated conductor stays insulated back to the source. And an isolated ground belongs only where it actually helps.

Units, terms, and abbreviations

Isolated ground work runs on a handful of terms and abbreviations that show up across drawings, cut sheets, and code, and they are easy to mix up with grounding terms that mean something different.

An isolated ground is written IG or IGR, for isolated ground receptacle, and the conductor is the isolated equipment grounding conductor. Do not read isolated as ungrounded or floating, which are different systems with different rules. The noise it targets is electromagnetic interference (EMI) or radio-frequency interference (RFI), often described as common-mode noise. The data-center alternative is the signal reference grid (SRG), also called a signal reference structure or zero reference grid.

IG / IGR
Isolated ground, and isolated ground receptacle, the orange triangle-marked device
Isolated EGC
The separate insulated equipment grounding conductor that serves only the isolated ground terminal, back to the source
EGC
Equipment grounding conductor, the normal fault-path ground that still grounds the box on an isolated ground circuit
EMI / RFI
Electromagnetic and radio-frequency interference, the electrical noise an isolated ground aims to keep off the ground path
Common-mode noise
Noise appearing between the grounded conductors and ground, as opposed to between the line conductors
SRG
Signal reference grid, the bonded mesh a data center uses instead of isolated grounds for a high-frequency reference
SDS
Separately derived system, such as an isolation transformer, with its own grounding point near the load

Related tools

Next step: Find laboratory electrical projects

FAQ

What is an isolated ground receptacle?

An isolated ground receptacle has its ground terminal insulated from the metal mounting strap, so the device grounds only through a separate insulated conductor run back to the source instead of through the conduit and box. The orange triangle identifies it. It serves sensitive electronics and is still a full safety ground.

Why is an isolated ground receptacle orange?

An isolated ground receptacle is orange, or carries an orange triangle on its face, because the code requires the marking so anyone can identify it without removing the device. The requirement is commonly at NEC 406.3(D) in recent editions. An orange body alone does not make a receptacle isolated; verify the insulated ground terminal.

Does an isolated ground still need a regular ground?

Yes. An isolated ground circuit needs two grounds: the normal equipment grounding conductor that grounds the metal box and raceway, and the separate insulated isolated ground conductor that serves only the receptacle. Skip the box ground and the enclosure is unsafe, because the isolated ground inside the device does nothing for the box.

Do isolated grounds actually reduce noise?

Sometimes, but often not. An isolated ground helps only when noise is genuinely on the equipment ground and the equipment references that ground for its signals, mostly older analog, audio, lab, and medical gear. Modern switch-mode electronics usually ignore the safety ground, so an isolated ground does nothing measurable for them.

Is an isolated ground the same as an ungrounded outlet?

No. An isolated ground receptacle is fully grounded; it just grounds through a separate insulated conductor instead of the conduit and box. An ungrounded or floating system has no intentional ground at all and follows different rules. An isolated ground still carries fault current back to the source and trips the breaker.

Can an isolated ground conductor pass through a subpanel?

Yes. The isolated ground conductor is permitted to pass through one or more panelboards without connecting to their grounding bars, and through boxes without bonding, so it can terminate at the source ground of the service or derived system. This pass-through is commonly tied to the NEC 408.40 exception; verify the adopted edition.

How do I test an isolated ground receptacle?

De-energized, confirm the ground terminal is open to the mounting strap with an ohmmeter, then trace the insulated conductor unbroken back to the source. Confirm the box is grounded separately. A plug-in tester shows a ground present but cannot confirm isolation or the box ground, so do not rely on it alone.

What is the difference between an isolated ground and a signal reference grid?

An isolated ground gives one piece of equipment a single dedicated ground path back to the source, which can help low-frequency analog noise. A signal reference grid is a bonded mesh tying everything to a common reference with many short paths, which works far better for high-frequency digital gear. Frequency decides which fits.

When is an isolated ground worth the extra cost?

An isolated ground is worth the extra conductor and labor only for a real, identified noise problem on equipment that references its ground. For most outlets and modern electronics it does no work. Before paying for it, rule out a shared neutral, harmonics, or signal grounding, and compare it against a dedicated circuit.

People also ask

Codes cited in this guide

This guide is written and reviewed against the published standards below. Always confirm the current adopted edition with the authority having jurisdiction.