kVA, or kilovolt-amperes, measures apparent power from RMS voltage and current, with the phase arrangement determining the calculation. Use line-to-line voltage for the balanced three-phase square-root-of-three formula; use voltage across the actual load for single phase. A power meter's kVA can also depend on its total-power calculation method, so reconcile that setting before comparing instruments or reconstructing kVA from other readings.

Apparent power, the vector sum of kW and kVAR that the conductors and transformer carry

Used across 3 Anvilfield field guides, most in Electrical.
Updated

Which voltage belongs in the kVA calculation?

Schneider Electric's transformer calculation guide gives single-phase kVA as V x I / 1,000 and balanced three-phase kVA as 1.732 x line-to-line V x line I / 1,000. A balanced 480 V load at 150 A therefore draws 124.7 kVA. Using its approximately 277 V line-to-neutral value in that same formula produces 72.0 kVA and understates the load.

The equivalent wye calculation is three times phase-to-neutral voltage times phase current. The two expressions agree when their voltages and currents describe the same balanced system. A 240 V single-phase, 30 A load is 7.2 kVA; adding a three-phase multiplier to it creates an error. Identify the connection before using a number copied from the transformer sizing record.

Why cos phi does not always recover total kVA

Fluke's 434-II/435-II/437-II user manual defines total power factor from full-spectrum real and apparent power, while displacement power factor uses the fundamental components. A nonlinear load can therefore display a displacement factor near unity while total power factor remains lower because harmonic current contributes to RMS current.

Use measured total kW divided by total power factor when reconstructing the same meter's apparent power. A 90 kW reading at 0.90 total PF gives 100 kVA. Substituting a 0.99 displacement factor produces 90.9 kVA and misses the current burden. Keep the PF register name with the value rather than recording only a number labeled PF.

Match the meter algorithm before comparing totals

Fluke's manual identifies Unified as the default power method for the 430 Series II and identifies the selectable Classic arithmetic method with a sigma symbol on power parameters. Schneider Electric's MicroLogic X guide separately offers vector and arithmetic total-power methods, with arithmetic as its factory setting. A meter disagreement can therefore come from different definitions of the total.

Record wiring mode, CT and VT ratios, total-power method, phase currents, and the time of the reading. Unbalanced or distorted loads need those details most. Use the EPMS metering guide for the measurement chain, then compare equivalent registers at the same load state.

Distinctions

kVAh
kVA is a power quantity at an operating condition. kVAh accumulates apparent power over time; it is not another spelling of the nameplate rating.

Frequently asked questions

Can I calculate three-phase kVA from one clamp reading?

The balanced formula assumes the phases carry the same current at corresponding voltages. Where the loads differ, record all phases and use a power analyzer configured for the actual wiring system.

Sources checked

Also defined as

  • Datacenter: Apparent power, the volts times amps the gear must carry
  • Rated apparent power in thousands of volt-amperes, the size of the transformer

Where this shows up

Next step: Map power service assets