MWBC means multiwire branch circuit: multiple ungrounded branch conductors use one shared grounded conductor within a defined supply arrangement. The source winding determines the return-current arithmetic. Two 20 A loads cancel in the neutral on opposite 120/240 V legs under equal-power-factor sinusoidal conditions; the same loads on two phases of 208Y/120 V produce 20 A in the neutral. That distinction belongs on the circuit record before a shared-neutral fault is diagnosed.
Multi-wire branch circuit: two opposite-phase hots sharing one neutral, with a simultaneous disconnect
Two 120 V branches can have different neutral arithmetic
For sinusoidal loads with equal power factor on opposite 120/240 V legs, neutral current is the magnitude of the difference between leg currents. With 20 A on one leg and 10 A on the other, it is 10 A. This follows from the 180-degree separation of the supply legs.
Two phases of a 208Y/120 V system are separated by 120 degrees. For equal-power-factor sinusoidal loads, their neutral current is the square root of IA squared plus IB squared minus IA times IB. Loads of 20 A and 10 A produce 17.3 A in the shared neutral. Two equal 20 A loads produce 20 A, not zero. Three balanced phase loads give the different three-way cancellation described in the MWBC guide.
A common disconnect does not identify the supply phases
OSHA 1910.305(a)(2)(viii) requires simultaneous disconnection of all ungrounded conductors of a temporary multiwire branch circuit at its originating outlet or panelboard. OSHA 1910.305 also recognizes approved breaker handle ties for that disconnect function. The rule concerns disconnection; phase identification remains another check.
OSHA 1910.304(b)(1) requires phase-and-system identification for accessible MWBC ungrounded conductors where a building contains more than one nominal voltage system, with the identification method posted at each branch-circuit panelboard. Record the source voltage and shared-neutral grouping in the panel directory; a handle tie alone does not prove the handles occupy the required phases.
An open neutral turns unequal loads into a voltage divider
Two resistive loads of 8 ohms and 16 ohms normally draw 15 A and 7.5 A on separate 120 V legs. If their common neutral opens while both remain connected across 240 V, the series current becomes 240 divided by 24, or 10 A. The loads then receive 80 V and 160 V.
Neither leg needs to exceed a 20 A breaker rating for the 160 V exposure to occur. Overcurrent protection therefore does not establish protection from this open-neutral condition. Identify shared-neutral continuity and the actual circuit arrangement when resolving unequal line-to-neutral voltage; a normal-looking breaker handle does not answer either question.
Distinctions
- Two circuits on one phase
- Sharing a return between same-phase circuits adds their current rather than producing the intended opposite-leg cancellation.
- Common trip
- Simultaneous manual disconnection and common automatic tripping are different functions. The circuit and protection requirements establish which device arrangement applies.
Frequently asked questions
Do two equal 120 V loads always cancel in the neutral?
They cancel on opposite legs of a 120/240 V supply under the stated sinusoidal conditions. Two phases of a 208Y/120 V supply do not have that same cancellation.
Can an open neutral damage equipment without tripping a breaker?
Yes. The 8-ohm and 16-ohm load calculation produces 160 V on one load while each leg carries only 10 A.
Sources checked
Also defined as
- Multiwire branch circuit, ungrounded conductors sharing one neutral, requiring simultaneous disconnect
- Multiwire branch circuit, two or three ungrounded conductors on different phases sharing one neutral