ANVILFIELD Try FieldOS

Field glossary

Terms — R

314 field terms starting with R, 44 with a full reference page. Each links to the Anvilfield guides where the term is used on the job.

R
Conductor resistance in ohms per 1000 ft, from NEC Chapter 9, Table 8 or Table 9In: Grounding system testing field guideLow-voltage landscape lightingGround resistance testingFormwork, shoring, and reshoring
R / P suffix
R is the receptacle (the slots in the wall), P is the plug (the blades on the cord)In: Receptacle types and NEMA configs
R-value
Thermal resistance of the insulation; figured on a taper as both an average and a thinnest-point minimumIn: Roof crickets and tapered insulation
R-value (installed)
Thermal resistance of the insulation at its installed, uncrushed thickness, the value the code checksIn: Duct insulation field guide
R-value / R per inch
Thermal resistance of the assembly, and the resistance of a single inch of a given boardIn: Roof insulation and cover board
R-value vs air leakage
R-value is resistance to conductive heat flow; air leakage is bulk air through gaps, carrying both heat and moistureIn: Building insulation and air sealing
Ra
Outdoor air rate required per unit area, in cfm per square footIn: Ventilation rate and outdoor air field guide
Raceway
An enclosed channel made to hold conductors, such as conduit or tubingIn: Wiring methods and conduit types
Raceway / raceback
The aluminum box or backing behind channel letters that holds the wiring and supplies and consolidates penetrationsIn: Electric sign installation
Rack and pinion
The toothed rack on the mast and the powered pinion gear that meshes with it to drive the platform up and downIn: Mast-climbing work platform safety
Rack BBU
Battery backup unit: a lithium battery in the rack or a sidecar shelf that carries the load through a blip and bridges to the generatorIn: Rack BBU and ride-through
Rack cooling index (RCI)
How well rack intake temperatures stay inside the ASHRAE recommended range, at the hot and cold endsIn: Delta-T and return temperature
Rack inlet temperature
The air temperature entering the equipment, judged against the ASHRAE TC 9.9 allowable envelope through the ride-throughIn: Integrated systems test (IST)In-row cooling commissioning
Rack PDU
The power distribution strip in the cabinet, in basic, metered, or switched grades, commonly 0U in the rear channelIn: Data center rack PDU typesRack-and-stack deployment field guide
Rack U
Rack unit, 1.75 in of vertical mounting space, the unit assets and rack space are measured inIn: DCIM and asset management
Rack-and-stack
The physical install of servers, storage, and network gear into racks after the facility is ready, plus the migrations that load workloads inIn: Rack-and-stack deployment field guide
Racking
Flexing a panel so it follows a slope while the pickets stay plumb, versus stepping it levelIn: Commercial fence and gate install
Racking / mounting
The structural hardware that holds the PV array on the roof and carries its load into the structureIn: Rooftop solar mounting and racking
Radius
The horizontal distance from the crane's center of rotation to the load; rated capacity drops as the radius growsIn: Crane and rigging safety
Radius of action
The distance from the vibrator head over which it actually consolidates concreteIn: Placement and consolidation
Radon
A radioactive gas from the natural decay of uranium in soil and rock, a leading cause of lung cancer indoorsIn: Radon and vapor-intrusion mitigation
Rain load
The structural load from ponded water plus hydraulic head, per ASCE 7, about 5.2 lb/sq ft per inchIn: Blue roof controlled-flow drainageRoof drainage and drain sizing
Rainfall intensity
Design rain rate in inches per hour for a return period, from the code map or NOAAIn: Gutters and downspouts
Rainscreen
A drained, vented gap behind the siding, made with furring, that lets the wall drain and dryIn: Siding installation
Raised access floor
A grid of removable panels on adjustable pedestals above the structural slab, with the void below used as a plenumIn: Raised floor vs slab design
Raised floor / slab
Access floor on pedestals with a plenum, versus racks on the structural slabIn: White space and gray space field guide
Random vs defined traffic
Random traffic moves any direction and uses FF/FL; defined traffic follows a fixed wheel path and uses F-min or wavinessIn: Floor flatness and levelness
Range
Hot water temperature entering the tower minus cold water temperature leaving itIn: Cooling tower types and operationCooling tower commissioning
RAP
Reclaimed asphalt pavement, the milled or crushed existing asphalt reused as aggregate and a binder sourceIn: Asphalt milling and cold planingAsphalt recycling and FDRAsphalt mix design (Superpave)
RAP / RAS
Reclaimed asphalt pavement and reclaimed asphalt shingles, recycled binder and aggregate reused in the mixIn: Warm mix asphalt (WMA)Asphalt plant productionAsphalt mix types by layer
Rapid shutdown
Reducing a building-mounted PV system's controlled conductors to a safe voltage quickly on a single action, for responder safetyIn: Solar PV O&M field guideSolar-ready roof provisionsPV rapid shutdown (NEC 690.12)PV system wiring (NEC 690)
RAPL / BMC
Running Average Power Limit, the CPU power-cap feature, and the baseboard management controller that enforces caps out of bandIn: Power capping and oversubscription
Rate of placement (R)
The vertical rise of fresh concrete in the form per hour, a main driver of form pressureIn: Formwork, shoring, and reshoring
Rate of rise
How fast the micron reading climbs after isolating the pump; its speed and shape separate a leak from moistureIn: Refrigerant evacuation field guide
Rated (1 to 4)
ANSI/TIA-942 level, a separate prescriptive system covering four domains, not interchangeable with TierIn: Data center tier classification
Rated capacity
The maximum platform load, people plus tools plus material, that the machine is rated to carry, de-rated by reachIn: Aerial lift and MEWP safety
Rated capacity / load chart
The weight the deck can carry and how it must be distributed, posted for the specific machine and configurationIn: Mast-climbing work platform safety
Rated fire media
Fire glass or lava rock made for fire features; regular stone traps moisture and can explodeIn: Outdoor fire feature guide
Rated point (100 percent)
The design condition, the rated flow at rated pressure the system was sized aroundIn: Fire pump acceptance test
Rating (2A:10B:C)
The classes an extinguisher covers and its tested capacity on Class A and B firesIn: Fire extinguisher classes and PASS guide
Raveling
Loose aggregate shedding from the surface, the leading pervious failure, from bad paste, low compaction, or poor curingIn: Pervious concrete field guideAsphalt driveway installation
Raveling / weathering
Surface loss of aggregate and graying as the binder oxidizes and hardens; a surface, not a base, problemIn: Asphalt distress and crack diagnosis
RBC / UBC
Rack bonding conductor to the grid and unit bonding conductor from equipment to the rack busbarIn: Data center grounding and SRG
RCC
Roller-compacted concrete, a zero-slump concrete placed by paver and compacted with rollersIn: Concrete pavement types
RCI
Rack Cooling Index; how well inlet temperatures sit inside the ASHRAE envelope, 100 percent is cleanIn: Data center airflow managementAirflow management and blanking panels
RCL
Refrigerant concentration limit per ASHRAE 15, the most refrigerant allowed in the smallest occupied room if it leaksIn: VRF commissioning field guide
RCM
Reliability-centered maintenance; sets each asset's strategy by criticality, function, and failure modesIn: Data center PM program
RCR
Room cavity ratio, a shape factor for the room that selects the CU from the tableIn: Commercial lighting design
RCSC
The Research Council on Structural Connections specification for high-strength bolted joints, including the snug-tight and pretensioned methodsIn: Data center structural QA
RDHx
Rear-door heat exchanger, a water coil replacing a rack's rear door that captures the server exhaust heat at the rackIn: Rear-door heat exchanger commissioning
RDMA / NVMe-oF
Remote direct memory access and NVMe over Fabrics, the network protocols that let remote flash feed GPUs at near-local speedIn: AI storage tier architecture
RDMA / RoCE / InfiniBand
Remote direct memory access for GPU fabrics, carried over Ethernet (RoCE) or InfiniBandIn: Spine-leaf network architecture
RDS
Refrigerant detection system, the sensor that triggers A2L leak mitigationIn: Refrigerant types and A2L
Re-commissioning (ReCx)
Commissioning again a building that was commissioned before and has driftedIn: Retro-commissioning existing buildings
Re-enterable device
A firestop pathway sleeve or box with a self-sealing intumescent insert that holds the rating as cable is added or removedIn: Cabling pathways and firestop
Re-entrant corner
An inside corner where stress concentrates and a crack tends to run out at about 45 degreesIn: Control joint layoutConcrete crack types and causes
Re-identification
Permanently re-marking a conductor to read as a different type where allowedIn: Conductor color code and phase ID
Reactance
AC opposition from the conductor's magnetic field, significant on large or long runsIn: Voltage drop field guide
Reactivation
Marketing back to past customers to win repeat work; the cheapest revenue most trade businesses haveIn: Customer database and CRM
Reactivation / regeneration air
The heated airstream that strips moisture off the desiccant and exhausts itIn: Desiccant dehumidification field guide
Reactive / preventive / predictive
Run-to-failure; scheduled on a calendar or runtime; condition-based, triggered by measured conditionIn: Predictive maintenance guide
Reactive maintenance
Run-to-failure repair after the equipment breaks; the exception on critical gear, never the planIn: Data center PM program
Reactivity coupon
A copper or silver strip exposed in the space; its corrosion thickness sets the severity levelIn: Zinc whiskers and contamination control
Reactivity monitoring
Exposing copper and silver coupons for a set period and reading the corrosion to classify the environmentIn: Zinc whiskers and contamination control
Ready-mix concrete
Concrete batched at a plant to a set recipe and delivered by truck ready to placeIn: Ready-mix ordering and delivery
Reality capture
Recording real-world conditions as measurable 3D data, the truth source you design and verify againstIn: Reality capture and scan-to-BIM
Rear-door heat exchanger
An air-to-liquid coil that replaces the rack's back door and cools the exhaust at the rackIn: Data center cooling system types
Rebar #4
Reinforcing bar 1/2 in across, the minimum rebar size for a concrete-encased electrodeIn: Ufer ground field guide
Rebar cage
The cylinder of longitudinal bars and spiral reinforcement that gives the shaft tension, shear, and bending capacityIn: Drilled piers and caissons
Rebar cage / bond beam
The cage is the tied grid of reinforcing bar that gives the shell its tensile strength; the bond beam is the thickened, extra-reinforced top perimeter that carries the tile, coping, and deck edge and ties the walls together.In: Commercial pool construction
Rebound
Aggregate-rich material that bounces off and must not be reincorporated; rises overhead and on dry-mixIn: Shotcrete and gunite field guide
REC / PPA
Renewable energy certificate (an attribute) and power purchase agreement (a contract for specific output)In: Data center sustainability reporting
Recall
The share of reference positives successfully found. Divide true positives by all reference positives, including misses. Report the reference coverage and matching rule beside the result.In: Building and asset intelligence glossary
Recap
The summary that rolls labor, material, DJE, and quotes into job cost, then adds overhead and profitIn: Electrical estimating and bidding
Receiver
The air storage tank that buffers demand and smooths pressure; an ASME pressure vesselIn: Compressed air piping design
Receptacle / outlet
The device a plug connects to; outlet is the broader code term for any point current is takenIn: Receptacle types and NEMA configs
Receptor
The open fixture that catches the indirect waste, usually a floor sink, with its own trap and ventIn: Indirect waste and air gap guide
Recirculation
Hot exhaust air pulled back into the equipment inlets, raising inlet temperature above supplyIn: Living wall and green wall systemsData center airflow managementDelta-T and return temperatureAirflow management and blanking panels
Recirculation loop
The supply-and-return circuit that keeps hot water moving so it is hot at the far fixtureIn: Hot water recirculation loopsWater distribution system types guide
Reclaimed / recycled water
Municipally treated wastewater delivered as a separate non-potable supply for approved usesIn: Reclaimed water and purple pipe
Recoat
Cleaning and re-coating the roof on a roughly 10 to 15 year cycle to renew the protectionIn: SPF roof field guide
Recombinant
The VRLA design that recombines about 95 to 99 percent of the gas back to water on normal chargeIn: Battery room ventilation and hydrogen safety
Recommended range
The conservative steady-state band, about 18 to 27 C (64 to 81 F) for all classesIn: Thermal envelope and setpoints
Reconciled allowance
A stated budget adjusted against agreed quantities or costs under written approval and payment rules.In: Pond maintenance pricing
Record drawing
The designer's official set, produced from the as-builts by screening and incorporating the changes; carries the design professional's reviewIn: As-built record drawings
Recordable
A work-related injury or illness meeting the 300 log criteria, such as treatment beyond first aid or days awayIn: Incident investigation
Recordable vs reportable
Recordable goes on the 300 log; reportable means the call to OSHA for a fatality or severe injuryIn: Construction safety program
Recover (overlay)
A new roof covering installed over the existing roof without removing itIn: Reroof: recover vs tear-off
Recover board
A dense board over the insulation or old roof that gives the membrane a hard baseIn: Reroof: recover vs tear-off
Recover vs restoration
A recover adds a roof covering over an existing covering; a protective coating has its own code classification and approved-system scopeIn: Roof coating restoration system
Recover vs tear-off
A new membrane over the old one (recover) versus stripping to the deck (tear-off); moisture and code layers decideIn: Roof maintenance program
Recoverable depreciation
Depreciation withheld from the initial payment and recoverable when policy settlement conditions are metIn: Storm and hail damage restoration
Recovered binder
The aged asphalt binder still coating the RAP aggregate, recovered or accounted for in the mix designIn: Asphalt recycling and FDR
Recovery
Removing refrigerant from a system into an external cylinder, required by EPA 608 before opening the systemIn: Refrigerant leak detection field guidePure water RO/DI field guide
Recovery rate (GPH)
Gallons per hour the heater raises across the cold-inlet temperature riseIn: Water heater sizing and selection
Recurring revenue
Revenue you can predict because it repeats on a schedule, from renewing agreements, rather than from one-off transactionsIn: Service agreements and recurring revenueContractor succession and exit planning
Red tag / correction notice
A failed inspection and the list of items to fix before a re-inspectionIn: Plumbing permit and inspection guide
Red-line
The mark made directly on the drawing, in red, to show a field change as it happens, with the date and reasonIn: As-built record drawings
Reducer
A change in pipe diameter, confirmed by the size callout on each side of the fittingIn: Plumbing isometric reading guide
Reduction cut
Shortening a limb back to a living lateral at least about a third the stem diameter, the alternative to toppingIn: Tree pruning and maintenance
Referral rate
The share of new customers sent by past customers; the cheapest lead source a trade business hasIn: Customer communication and reviews
Reflectance / ORL
Light reflected by one event, and total reflected by the link; more negative is betterIn: Fiber OTDR certification
Reflected apparent temperature
The temperature of the surroundings that reflects off the target and into the camera, which corrupts the reading on low-emissivity metalIn: Infrared thermography field guide
Reflected ceiling plan (RCP)
The plan view of the ceiling looking up, showing the grid, borders, and every light, diffuser, and deviceIn: Suspended acoustical ceiling field guide
Reflected wave
Voltage doubling at the motor terminals from impedance mismatch on a long cable runIn: VFD install and commissioning
Reflective cracking
A crack or joint in an underlying layer propagating up through an overlay in the same patternIn: Asphalt distress and crack diagnosisConcrete overlay and resurfacing
Reflective cracking / interlayer
The old crack reappearing through the overlay, and the stress-relief layer (SAMI, fabric, geogrid) that slows itIn: Asphalt mill and overlay
Refrigerant stacking
Refrigerant pooling in the condenser at high load and very low condenser-water temperature, costing capacityIn: Chiller plant sequencing optimization
Refrigeration rack
Parallel compressors on shared piping feeding a store, split into medium-temp and low-temp suction groups, with staged capacity and redundancyIn: Commercial refrigeration field guide
Refusal
When a pier stops advancing before design depth against rock, cobbles, or fill; resolved by relocating, advancing past, or load testing, not forcing.In: Helical piers and screw piles
Refusal and set
The point where the pile stops advancing under the hammer, and the penetration per blowIn: Driven pile foundations
Regeneration / reactivation
Heating the loaded desiccant to drive the held moisture back off into an exhaust airstreamIn: Desiccant dehumidification field guide
Registered apprenticeship
A program approved by the DOL or a state agency to standards at 29 CFR Part 29, earning a recognized credentialIn: Apprenticeship and training program
Registration
Stitching individual scans into one aligned cloud, target-based or cloud-to-cloud, reported with a registration errorIn: Reality capture and scan-to-BIMWarranty claim processing guide
Reglet
A saw-cut groove in masonry that holds a counterflashing, sealed to keep water out of the cutIn: Roof penetration flashingParapet base flashing detailRoof flashing types
Regular rate
The pay rate the overtime multiplier applies to, which can include more than the base hourly wageIn: Field time tracking and labor hours
Regulated medical waste
Contaminated material handled under medical-waste rules: red-bagged or in sharps containers, manifested, and sent to licensed disposalIn: Biohazard and trauma cleanup guide
Regulated waste
Asbestos debris that must be wetted, double-bagged, labeled, manifested, and disposed of at a permitted facilityIn: Asbestos abatement procedures
Rehabilitation / reconstruction
Restoring structure and ride to failed-down pavement, versus rebuilding failed pavement from the subgrade up; neither is preservationIn: Pavement preservation treatments
Reheat
Adding heat to dehumidified air to raise its supply temperature, ideally from recovered heat rather than new energyIn: DOAS field guide
Reheat dead band
The temperature range where the box holds minimum airflow with the reheat valve shutIn: VAV box commissioning field guide
REI
Restricted-entry interval, the label time after application before re-entry without the required PPEIn: Landscape IPM field guide
Reimbursable
A job cost billed back to the customer, usually with a contract markup, as opposed to overhead the company absorbsIn: Job expense and receipt tracking
Reinforced zone
The compacted, grid-bound block of soil behind the face that acts with the wall as a mechanically stabilized earth massIn: Segmental retaining wall build
Reinforcement fabric
Polyester fabric embedded in the coating at seams, laps, and fastener rows for tensile strength and crack-bridgingIn: Roof coating restoration systemMetal roof restoration
Reinforcing mesh
Alkali-resistant fiberglass embedded in the EIFS base coat for impact and crack resistanceIn: Stucco and EIFS
Rejuvenator
A product that penetrates and restores aged asphalt binder by replacing lost maltenes, softening it and bringing back flexibilityIn: Fog seal and rejuvenator preservationAsphalt recycling and FDR
Rejuvenator / recycling agent
An oil or additive that restores lighter fractions to aged binder, softening it back toward fresh behaviorIn: Asphalt recycling and FDR
Related instruction (RTI)
The classroom or online theory, code, and safety, commonly about 144 hours per year in a registered programIn: Apprenticeship and training program
Relative compaction
In-place dry density as a percentage of the Proctor maximum dry densityIn: Pavement base and subgrade compaction
Relative humidity
The water vapor present compared to the maximum at that temperature, in percent; a ratio, not a quantityIn: Psychrometric chart
Relative humidity vs dew point
RH is how full the air is as a percent; dew point is the temperature at which water condenses, and it sets which surfaces sweatIn: Natatorium HVAC field guide
Release agent
A bond breaker that keeps the stamp from sticking; pigmented powder versions also leave a secondary accent colorIn: Stamped concrete install guide
Release agent (form oil)
The film applied to the form face so it strips clean without bonding to or staining the concreteIn: Formwork types and systems
Release detection / ATG
Required monitoring that finds a UST leak early; an automatic tank gauge is one in-tank method, interstitial monitoring is the method for new secondarily contained systemsIn: Fuel storage tank field guide
Release rate
The maximum the site may discharge, set by the stormwater authority, often in cfs per acreIn: Blue roof controlled-flow drainage
Relief air
The planned path that lets a positive building bleed its surplus out, gravity or poweredIn: Building pressurization field guide
Relief valve opening point
The differential at which an RP's relief valve starts to discharge the zone, commonly 2.0 psid or greaterIn: Backflow test procedure guide
Relief vent
A second air path on a circuit-vented branch with four or more closets tying into a stack loaded from aboveIn: Wet venting and common vent guide
Remainder / balance
The conductor left on a reel after one or more pullsIn: Cable reel receiving and remainder log
Remaining service life
The estimated number of years a roof has left before it needs replacementIn: Roof asset management
Remote hands / smart hands
Provider technicians doing physical work (remote) or technical work (smart) in your space when you are not on siteIn: Colocation fit-out field guide
Remote-hands
A local or dispatched technician who does the physical task the remote team cannot, under guidanceIn: Edge and micro data center deployment
Renewal rate / churn
The share of expiring agreements that renew, and its mirror, the share that leave; two views of whether the base holdsIn: Service agreements and recurring revenue
Renovate Right
EPA's lead-hazard pamphlet that the firm must deliver to owner and occupants before a covered renovationIn: Lead-safe renovation (RRP)
Rent commencement
The lease date the tenant starts paying rent, which the fit-out schedule is built to meetIn: Tenant improvement fit-out
Rental period
The billable equipment possession period defined by the agreement, kept separate from engine operating hours.In: Temporary power rental prospects
Repair behind the bar
Removal around corroded reinforcement to expose its full circumference and provide the clearance specified for the repair materialIn: Parking structure restoration
Repair, restore, replace
The three actions: fix a local defect, coat or recover a worn but sound roof, or tear off and rebuildIn: Roof asset management
Repeat rate
The share of work that comes from customers you have served before; a direct measure of whether follow-up is workingIn: Customer communication and reviews
Repellent
A scent or taste product that makes a plant unpleasant, reducing browse but not eliminating it, and subject to wash-off and habituationIn: Deer and wildlife protection
Replace vs restore
The adjuster's item-by-item call: restore when it costs less than replacement, replace when it does notIn: Contents pack-out and inventory
Repointing
Removing deteriorated outer mortar from joints and replacing it with fresh, compatible mortarIn: Masonry repointing and restoration
Reportable
An event that triggers direct notification to OSHA on a clock: fatality, in-patient hospitalization, amputation, or eye lossIn: Incident investigation
Reported capacity
A capacity value attributed to a specific record, retaining its units and evidence date; it does not establish current contents or usable inventory.In: Tank-facility directory research
Reported problem
What the caller said was wrong, in their words, before diagnosisIn: Work order management field guide
Reporting boundary
The defined line around what counts as facility, IT, and another party's responsibilityIn: Data center sustainability reporting
Reporting time pay
Show-up pay, the minimum some states or CBAs require when you report and the work is not thereIn: Hours, overtime, and per diem proof
Rescue plan
The site-specific plan to bring a stranded or fallen worker down under control before suspension trauma sets inIn: Suspended scaffold and swing stage safety
Reserve alkalinity
A titration that measures the buffer left in the fluid; falling against baseline means the inhibitor is depletingIn: Hydronic water and glycol field guide
Reserve area
Suitable soil set aside and protected for the future replacement field, required by many codesIn: Septic system field guide
Reservoir void ratio
The share of the open-graded stone layer that is open space, commonly near 40 percent, where the water storesIn: Permeable pavement install
Residual pressure
The flowing pressure left at a fixture while water is running, what proves the far fixture is servedIn: Booster and PRV system guideLow water pressure guideWater distribution system types guideWater supply pipe sizing guide
Residual rate
The amount of actual asphalt left after the water or solvent leaves, the number specifications set for tackIn: Tack and prime coatAsphalt mill and overlay
Residual sensing
Summing CTs on all three phases and the neutral, where the net should be zeroIn: GFPE field guide
Residual strength
The load a fiber concrete carries across a crack after cracking, measured by ASTM C1609 or C1399In: Fiber-reinforced concrete
Residual value
The resale or salvage value expected at the end of the machine's working lifeIn: Equipment cost recovery and own vs rent
Resilient flooring
Hard, wipeable floor covering: LVT, LVP, VCT, sheet vinyl, rubber, and linoleumIn: Commercial resilient flooring install
Resilient modulus (Mr)
The stiffness of the subgrade under repeated wheel loading, the main subgrade input to AASHTO designIn: Asphalt pavement thickness design
Resistive vs reactive bank
Resistive loads at unity PF (engine only); reactive adds kVAR to test the alternator and AVR at rated currentIn: Generator load bank testing
Resistivity
Water's resistance to current, in megohm-cm at 25°C; higher is purer, ~18.2 is ultrapureIn: Pure water RO/DI field guide
Respirable crystalline silica
The fraction of silica dust fine enough to reach deep into the lungs, released by cutting, grinding, drilling, or breaking concrete, masonry, stone, or brickIn: Siding installationSilica exposure control programSilica dust control methodsConcrete cutting and coring
Restoration
Re-grinding and re-polishing an existing terrazzo floor back to a new finish, the reason terrazzo lasts for generationsIn: Terrazzo flooring install and polish
Restoration coating
A fluid-applied membrane coated over an existing sound roof to renew it and extend its life without a tear-offIn: Roof coating restoration system
Restrained joint
A pipe joint that carries tension, locking the pipe so it resists pulloutIn: Thrust restraint field guide
Restrained length
The length of pipe each side of a fitting that must be restrained so soil friction holds the thrustIn: Thrust restraint field guide
Restraint
Anything that stops concrete moving freely as it shrinks or contracts, turning movement into tensionIn: Concrete crack types and causes
Retail vs wholesale colo
Retail sells by the cabinet or cage in shared halls; wholesale sells suites or data halls, usually 100 kW and up, with more tenant controlIn: Colocation fit-out field guide
Retainage
A percentage, often 5 to 10 percent, held back from progress payments until project closeoutIn: Closeout and warranty managementSubcontractor managementCash flow and forecasting field guideAR and collections field guide
Retainage / retention
The percentage of payment withheld until completion, commonly reduced at substantial completion and released at final; set by contract and statuteIn: Retainage and retention field guidePunch list and closeoutOwner-ready reports and billing backup
Retainage receivable / payable
Retainage held from you is an asset (receivable); retainage you hold from subs is a liability (payable); ask a CPA about classification and timing.In: Retainage and retention field guide
Retempering
A one-time, recorded jobsite water addition allowed under ASTM C94 within the design w/c limitIn: Concrete slump test
Retention
Storage terminology that varies by jurisdiction; identify whether the approved facility retains a permanent poolIn: Detention and retention pondsCCTV system design field guide
Retention / churn
Keeping trained staff versus the rate at which they leave; churn costs the person, the knowledge, and the training investmentIn: Data center staffing and workforce
Retention / hold time
The minimum time the room must hold the agent at the protected height, commonly at least 10 minutes under NFPA 2001In: Clean agent room integrity
Retention bond
A surety bond posted in lieu of cash retainage so the held money is freed while the owner keeps equivalent security; availability varies by contract and state.In: Retainage and retention field guide
Retention pond
A stormwater pond with a permanent pool that adds water-quality treatment to peak flow control.In: Detention and retention ponds
Retention time
The minutes wastewater stays in the tank, the basis of gravity interceptor sizingIn: Grease interceptor field guide
Retro-commissioning
Tuning existing equipment and controls back to proper operation; an audit finds the waste, retro-commissioning corrects the operational part.In: Energy audit and management field guide
Retro-commissioning (RCx)
The first commissioning of an existing building that was never commissionedIn: Retro-commissioning existing buildings
Retroreflectivity
Light from a headlight returned toward the driver by glass beads, measured in mcd/m2/lux at 30-meter geometryIn: Pavement marking and stripingPavement marking materials and application
Return loss
Signal reflected by an impedance change; a kink or an over-cinched tie throws itIn: Cat6A certification field guide
Return static
Static pressure at the manufacturer's designated inlet test locationIn: External static pressure field guide
Return temperature
The temperature of the water coming back to the heater, held above the growth-band floorIn: Hot water recirculation loops
Return temperature index (RTI)
Unit delta-T divided by IT delta-T, as a percent; below 100 is bypass, above 100 is recirculationIn: Delta-T and return temperature
Reveal
The deliberate, consistent gap around a door, drawer, or panel; the consistency is the quality tellIn: Millwork and casework install
Revenue grade
Metering accurate enough to bill against, commonly ANSI C12.20 Class 0.2 or 0.5In: EPMS and power metering
Revenue-grade
Meter accurate enough to bill against, meeting ANSI C12.20, typically Class 0.2 or 0.5In: Submetering and energy monitoring
Reverse power (32)
Protection that trips a set being motored, when real power flows into it instead of outIn: Generator paralleling
Reversing valve
Four-way valve that reverses refrigerant flow to switch a heat pump between heating, cooling, and defrostIn: Heat pump fundamentals field guideReversing valve and defrost field guideSplit-system install field guide
Reversing valve (O/B)
The heat-pump valve that switches between heating and cooling, driven by the O or B terminalIn: Thermostat types and wiring field guide
Review velocity / recency
How steadily and how recently new reviews arrive; a steady weekly flow ranks better than a large pile of old reviewsIn: Customer communication and reviews
Revise and resubmit
A review stamp returning a submittal for correction, which restarts the review clockIn: RFI and submittal process
REX (request-to-exit)
A button or sensor that tells the controller a legitimate exit is happening so it does not alarm; it is not the means of egressIn: Access control system field guide
RF exposure zone
An access area evaluated under FCC exposure limits and the conditions for controlled or general-public exposureIn: Cell tower and antenna install
RFI
Request for information, the formal question whose answer often moves the work; its number ties to the resulting red-lineIn: RFI and submittal processAs-built record drawings
RFID vs BLE vs UWB vs GPS
Location technologies ordered by precision and cost: RFID is cheap read-or-no-read, BLE is zone level, UWB is sub-meter, GPS is outdoorIn: Connected jobsite and RTLS
RGA / RMA
Return goods or materials authorization; the number that allows the defective part to be returnedIn: Warranty claim processing guide
RH
In-slab relative humidity as a percentage, read by an in-situ probe at depth (ASTM F2170)In: Slab moisture testing for flooring
RH (ASTM F2170)
Relative humidity inside the slab, read by in-situ probe as a percentageIn: Self-leveling underlayment floor prepEpoxy resinous floor coating install
RH (relative humidity)
Relative humidity of the air in the test hole at slab temperature, expressed as a percentage; not the percentage of water by mass in concreteIn: Slab moisture testing for flooring
Rhizome / stolon
Spreading stems, below ground (rhizome) or above (stolon), that let a grass fill in and self-repairIn: Turfgrass selection
RHO
Thermal resistivity of the soil or backfill in degrees C-cm per watt; lower RHO carries heat away and raises ampacityIn: Concrete-encased duct bank field guide
RICE NESHAP
40 CFR Part 63 Subpart ZZZZ, hazardous-air-pollutant standards for reciprocating enginesIn: Generator emissions and permitting
Ride-through
The window between a power or cooling loss and full recovery, during which the critical load and room temperature must holdIn: Thermal energy storage tankIntegrated systems test (IST)
Ride-through / hold-up
The short window the BBU carries the load, sized to the generator start, not to long runtimeIn: Rack BBU and ride-through
Ridge-to-valley depth (RVD)
The height of the milled texture, from a ridge top to a valley bottomIn: Asphalt milling and cold planing
Riding the curve
How the operating point slides along the pump curve when a valve throttles or the system resistance changesIn: Hydronic pump install field guide
Right plant, right place
Selecting a plant whose sun, soil, water, and mature-size needs match the conditions of its spot so it thrives with little inputIn: Landscape design and plant selection
Rigid / PCC pavement
A portland cement concrete slab that carries load by beam action, as opposed to flexible asphaltIn: Concrete pavement typesConcrete pavement jointing and curing
Rigid frame / primary framing
The built-up tapered columns and rafters that form the main moment-resisting structure and carry the load to the anchor boltsIn: Metal building erection
Rigid pavement
Concrete pavement, a stiff slab that bridges and distributes load by beam actionIn: Asphalt vs concrete pavement
Riser
A vertical supply pipe carrying water up to the floors and branchesIn: Plumbing isometric reading guideBusway installation field guide
Riser (CMR/CL2R/FPLR)
The cable rating for vertical runs between floors; passes a floor-to-floor flame testIn: Low-voltage and Class 2 cabling
Riser clamp
A clamp whose ears bear on the floor structure to support a vertical pipe at each floorIn: Pipe hangers and seismic bracing guide
Riser diagram
A flat schematic of the vertical stacks and risers floor to floor, often single-lineIn: Plumbing isometric reading guide
Risk rating
The matrix output, low, moderate, high, or extreme, that drives the monitor, mitigate, or remove decisionIn: Tree risk assessment
Risk register
The list of identified risks behind the contingency, each scored by likelihood and impact, used to size and then draw down the contingency.In: Contingency and risk pricing
Risk reserve
Money carried for identified uncertainty, consumed before the same disruption reduces planned profit.In: Public paving bid-or-pass worksheet
RMC / IMC / EMT
Rigid metal conduit, intermediate metal conduit, electrical metallic tubingIn: Wiring methods and conduit types
RO / permeate / reject
Reverse osmosis; the purified water through the membrane is permeate, the concentrated leftover is reject or concentrateIn: Pure water RO/DI field guide
Robotic total station
A one-person instrument that measures angle and distance to a tracked prism, accurate to a few millimeters, for building layoutIn: Construction layout
RoCE
RDMA over Converged Ethernet, running RDMA on Ethernet made lossless with PFC and ECN, versus InfiniBand's credit-based lossless fabricIn: Network observability for the AI fabric
Rodding / jetting
Clearing a drain with a powered cable, or with a high-pressure water hoseIn: Plumbing cleanout field guide
Roll to seat
Rolling porous asphalt only enough to lock the mat, not to chase density, so the surface voids stay openIn: Permeable pavement install
Roller / glide support
A support that lets pipe slide as it expands and contracts, so it does not abrade the roof or stress fittingsIn: Rooftop equipment supports and walkways
Roller tube screed
A spinning tube pulled across the surface; handles slopes, less operator-dependentIn: Laser screed and screeding methods
Rolling load
Dynamic load from a wheel rolled across the panel for a set number of passes, the data-hall case that usually governsIn: Structural design for AI racksRaised floor acceptance packetRaised floor load rating test
Rolling pattern
The fixed pass count, overlap, speed, and gap each roller runs, set on a test strip and held to keep density uniformIn: Asphalt compaction and rolling
Rolling sphere
A design sphere, commonly 150 ft radius, rolled over the structure to find exposed points needing terminalsIn: Lightning protection (NFPA 780)
Roof area
The roof surface quantity defined for a particular measurement or scope. Record whether it is projected area or actual sloped surface area and how openings, overhangs and separate roof sections were treated.In: Building and asset intelligence glossary
Roof asset management
Treating each roof as a tracked capital asset: inventory, condition rating, remaining-life estimate, and a multi-year capital planIn: Roof asset management
Roof condition index
A condition score interpreted through its stated method, supported by dated observations of the roofIn: Roof asset management
Roof condition rating
A consistent score of a roof's overall condition used to estimate remaining life and plan capitalIn: Roof maintenance program
Roof curb
The steel frame that carries the unit, routes the duct through the roof, and seals it watertightIn: RTU install and startup field guide
Roof expansion joint
The watertight roof detail over a structural expansion joint, built on two raised curbs with a flexible cover spanning the gap to take the building's movementIn: Roof expansion joint installation
Roof hatch / scuttle
Hinged insulated cover on a curb that frames the opening through the roofIn: Roof hatch access and fall protection
Roof moisture survey
An infrared scan, usually after sunset, that locates wet insulation by the heat it retains, per ASTM C1153.In: Drone inspection field guide
Roof snow load
The design snow weight on the roof, derived from the ASCE 7 ground snow load and its factors, in psfIn: Snow guards and retention
Roof tarping (dry-in)
Temporary weatherproofing of a damaged roof with poly sheeting, run and anchored so water sheds off the buildingIn: Emergency board-up and tarping
Roofing square
100 square feet of roof area, the unit of measure and pricingIn: Reroof: recover vs tear-off
Rooftop avalanche
The sudden release of a whole snowpack off a slick or steep roof, the hazard retention is built to preventIn: Snow guards and retention
Rooftop unit
A self-contained HVAC unit with cooling, heating, fans, and often an economizer in one cabinet on a roof curbIn: RTU install and startup field guide
Room integrity / door fan test
A pressurization test that measures enclosure leakage to confirm a clean agent room holds concentration for the required timeIn: Data center fire and life safety
Room pressure monitor
A permanently installed instrument that continuously shows the pressure direction at the door and alarms when it is lostIn: Healthcare HVAC ventilation field guide
Root ball
The mass of soil and roots dug with the tree, sized by trunk caliper per ANSI Z60.1In: Tree transplanting
Root barrier
A layer, or a certified root-resistant membrane, that keeps roots from penetrating the waterproofingIn: Green roof installation
Root cause
The actual underlying reason a callback happened, usually a crew, a detail, or a product, as opposed to the symptom you fixed on the visit. Fixing it removes future callbacks instead of just covering them.In: Warranty reserve and cost management guideIncident investigation
Root cause analysis (RCA)
The structured search after restore for the real cause and contributing factors, not the first symptom, often using the 5-whysIn: Incident management and outage response
Root flare
The point where the trunk widens into the first main roots, which must sit at the surface and stay exposedIn: Commercial maintenance programMulch beds and weed controlTree transplantingPlant health care (PHC)
Root flare / trunk flare
Where the trunk widens into the first main roots; it must sit at or just above finish gradeIn: Tree and shrub planting
Root pruning
Cutting a ring of roots months to a year ahead so fibrous roots regrow inside the future ball lineIn: Tree transplanting
Root zone
The depth of soil the plant's active roots occupy, which a cycle should wet and then let dryIn: Irrigation controller programming
Root-cause code
The reason a callback happened: workmanship, bad part, misdiagnosis, or rushedIn: Callback and warranty tracking guide
Rootzone
The engineered soil or sand layer the turf roots into, built to drain and resist compactionIn: Sod and turf establishmentSports field construction
Rope / cable sensor
A continuous linear element that senses fluid anywhere along its length and reports the location, for distributed coverageIn: Liquid-cooling leak detection
Rotation / changeout
A scheduled replacement of the color display, pulling the spent planting and installing the next season's flowersIn: Seasonal color and annual rotation
Rough-in
The drain, vent, and supply piping set to a fixture in the open wall and floor, tested and inspected before the surfaces closeIn: Plumbing permit and inspection guideFixture rough-in and setting guide
Rough-in sheet / cut sheet
The manufacturer's dimensioned drawing for a fixture, giving drain, supply, and clearance dimensions from the finished surfacesIn: Fixture rough-in and setting guide
Rough-in test
The test of the bare piping before fixtures and before close-in, proving the joints holdIn: Plumbing pressure test guide
Route and seal
Widening a non-structural crack into a groove and filling it with a flexible sealantIn: Concrete crack injection
Route contribution
Route revenue minus the explicitly defined direct delivery costs, leaving money for overhead and profit.In: Service territory planning
Route density
The concentration of schedulable stops along a workable route, judged with travel, service duration, and access windows.In: Service territory planning
Rp
Outdoor air rate required per person, in cfm per person, from the 62.1 occupancy tableIn: Ventilation rate and outdoor air field guide
RP / RPZ
Reduced pressure principle assembly; two checks plus a relief valve, for high hazard and both flow directionsIn: Cross-connection controlBackflow test procedure guide
RP / RPZ / RPBA
Reduced pressure zone assembly; two checks plus a relief valve, for high hazard and both backflow mechanisms (ASSE 1013)In: Backflow assembly types
RP assembly
Reduced-pressure principle backflow assembly protecting the potable makeup connectionIn: Reclaimed water and purple pipe
RPO
Recovery point objective, the maximum tolerable data loss, measured in time back to the last good copyIn: Data center disaster recovery
RPP
Remote power panel, a panelboard fed from the PDU and placed near the rows to shorten branch runsIn: Data center power distribution chainPDU and RPP commissioning
RPZ / RP
Reduced pressure principle assembly, the highest-protection testable backflow assembly (ASSE 1013)In: Backflow failed test repair guide
RPZ backflow preventer
A reduced-pressure-zone assembly that stops sump water from siphoning into the potable supplyIn: Sump pump backup protection guide
RRP Rule
EPA's Renovation, Repair, and Painting Rule (40 CFR 745, Subpart E) for work that disturbs lead paint in pre-1978 homes and child-occupied facilitiesIn: Lead-safe renovation (RRP)
RRP vs abatement
RRP is renovation that controls lead dust along the way; abatement is work whose purpose is to permanently remove lead, under separate stricter rulesIn: Lead-safe renovation (RRP)
RRU / antenna
Remote radio unit, the transceiver mounted at the antenna, and the antenna panel that radiates each sectorIn: Cell tower and antenna install
RTE
Round-trip efficiency, energy out on discharge divided by energy in on chargeIn: BESS commissioning punch list
Rtg / Rg
Resistance-to-ground, measured from one floor electrode to the bonded ground pointIn: ESD floor testing field guide
RTI
Return Temperature Index; above 100 percent is recirculation, below 100 percent is bypassIn: Data center airflow managementAirflow management and blanking panels
RTI = 100%
Unit delta-T matches IT delta-T; the supply air does its work and returns fully heatedIn: Delta-T and return temperature
RTI above 100%
Recirculation; rack airflow exceeds cooling airflow and exhaust is pulled back to the inletsIn: Delta-T and return temperature
RTI below 100%
Bypass air; cooling airflow exceeds rack airflow and cold supply short-circuits to the returnIn: Delta-T and return temperature
RTLS
Real-time location system, tracking the position of tagged assets or people against fixed reference pointsIn: Connected jobsite and RTLS
RTO
Recovery time objective, the maximum tolerable downtime before a system must be restoredIn: Data center disaster recovery
Rtt / Rp
Point-to-point resistance, measured between two electrodes on the floor surfaceIn: ESD floor testing field guide
RTT / RTG
Resistance point-to-point and resistance-to-ground, the ESD floor measurements per ANSI/ESD STM7.1In: Raised floor acceptance packet
RTU / AHU / FCU
Rooftop unit, air handling unit, and fan coil unit, the common air-side equipment namesIn: HVAC system types field guide
RTU / AHU / VAV / VRF
Rooftop unit, air handler, variable-air-volume box, and variable refrigerant flowIn: HVAC estimating and bidding field guide
RTU / packaged unit
A self-contained HVAC unit with cooling, heating, fans, and often an economizer in one cabinet on a roof curbIn: RTU install and startup field guide
RU / U
Rack unit, 1.75 in of vertical mounting height; an open U is a recirculation path without a blanking panelIn: Rack readiness field guideAisle containment QA
Rule of 20 percent
Acclimatization ramp: about 20 percent of normal workload day one, adding roughly 20 percent each dayIn: Heat illness prevention
Rule-based vs data-driven
Rules encode physics or sequence logic and are transparent; data-driven methods learn normal patterns and flag anomaliesIn: FDD and building analytics field guide
Runbook
The step-by-step migration plan with owners, order, dependencies, downtime, and a defined rollbackIn: Rack-and-stack deployment field guide
Running bond
The brickwork-style staggered joint pattern that keeps sod seams from lining upIn: Sod and turf establishment
Running slope
The slope down the ramp run in the direction of travel, held to 8.3 percent (1:12) maximumIn: ADA curb ramp and detectable warning
Running vs stack bond
Running bond provides the required unit overlap; other bond patterns need their approved continuity and reinforcement detailsIn: CMU block wall construction
Runoff coefficient
The fraction of rainfall a catchment surface actually sheds to collection, around 0.9 for clean metalIn: Graywater and rainwater harvesting
Rupture basin
An open-top containment under the day tank sized to hold the full tank volume, with a leak alarmIn: Generator fuel system and day tank
Rust converter
A phosphoric-acid product that turns flaky iron oxide into a stable iron phosphate the primer can bond toIn: Metal roof restoration
Rust-inhibitive primer
A primer, often zinc-phosphate based, that binds remaining rust and blocks moisture before the coatingIn: Metal roof restoration
Rut box
A spreader box with V-shaped screeds that fills wheelpath ruts with micro-surfacing before a surface courseIn: Slurry seal and micro-surfacing
Rutting
A wheelpath depression from deformation or consolidation in the asphalt, base, or subgradeIn: Asphalt distress and crack diagnosis
RV
Relief valve, the part on an RP that dumps the zone to atmosphere when a check failsIn: Backflow failed test repair guide
RVS / RVSS
Reduced-voltage starting, and the solid-state soft starter version of itIn: Motor starting methods
RWL
Recommended weight limit, the NIOSH equation output for a specific liftIn: Material handling and lifting ergonomics

All glossary terms

On the job

Crews log these terms against real jobs in FieldOS, then hand the customer a clean proof page. See how FieldOS works.